background image

Architectural and Engineering

Specifications

 

The smoke alarm shall be Kidde Model i4618 or approved equal. It 

shall be powered by a 120VAC, 60Hz source along with a 9V battery back-

up. The unit shall incorporate an ionization sensor with nominal sensitivity 

of 0.50 to .92%/ft. The temperature operating range shall be between 40°F 

and 100°F (4°C and 38°C) and the humidity operating range shall be up to 

85% relative humidity.
 

The smoke alarm can be installed on any standard single gang electri-

cal box, up to a 4” octagon junction box. The electrical connection (to the 

alarm) shall be made with a plug-in connector. A maximum of 24 Kidde 

devices can be interconnected in a multiple station arrangement. The 

interconnect system must not exceed the NFPA (National Fire Protection 

Association) limit of 18 initiating devices, of which 12 can be smoke alarms. 

With 18 initiating devices (Smoke, heat, CO, etc), interconnected, it is still 

possible to interconnect 6 strobe lights and/or relay modules. The alarm 

shall provide optional tamper resistance that deters removal of the unit 

from the wall or ceiling. No additional pieces shall be required to activate 

this feature.
 

The alarm shall include an easy access battery compartment that is 

opened and closed by sliding the battery door. The 9V battery carrier will 

ensure proper battery backup protection by not allowing the battery door  

to close if the battery is placed in the unit incorrectly or if a battery is not 

present.  
 

The unit shall include a piezoelectric horn that is rated at 85 decibels 

at 10 feet. The unit shall include the Smart Hush

TM

 feature that silences the 

unit for approximately 8 minutes if a nuisance condition occurs. 
 

The unit shall incorporate red and green LED indicators. The green  

 LED (when illuminated) indicates the presence of AC power. The red LED  

(located under the TEST/Hush button) has four modes of operation:
 

Standby Condition:

 The red LED will flash every 30-40 seconds to indi-

cate that the smoke alarm is operating properly. 

Alarm Condition:

  When 

the alarm senses products of combustion and goes into alarm the red LED 

will flash one flash per second. The flashing LED and pulsating alarm will 

continue until the air is cleared. When units are interconnected, only the red 

LED of the alarm that senses the smoke or is being tested (the originating 

unit) will flash. All other units in the interconnected system will sound an 

alarm but their red LED’s will NOT flash. 

Alarm Memory:

  This smoke alarm 

is equipped with an alarm memory, which provides a visual indication when 

an alarm has been activated. The red LED will illuminate for about 1.5 

seconds every 16 seconds to indicate the memory condition. 

Smart Hush

TM

 

Mode:

  The red LED will illuminate for 1.5 seconds every 8 seconds,  

indicating the smoke alarm is in the Smart Hush

TM

 Mode. 

 

The unit shall at a minimum meet the requirements of UL217, NFPA72, 

and (chapter 11), The State of California Fire Marshall, NFPA101 (0ne and 

two family dwellings), Federal Housing Authority (FHA), Housing and Urban 

Development (HUD).

FUSE OR CIRCUIT BREAKER

BLACK

WHITE

RED

L
N

First 

Alarm

Additional 

Alarms

Ordering Information

Ordering  

 

 

 

Dimensions 

Number 

UPC 

I2F5 

Pack Quantity 

(w x d x h inches) 

Weight  Skid 

21007581 

0-47871-07581-2 

100-47871-07581-9 

Cut Case (6 units) 

6.63 x 13.25 x 6.25 

3 lbs 

1008

21007584 

0-47871-07584-3 

100-47871-07584-0 

Bulk Pack (36 units) 

13.25 x 19.5 x 19.5 

18 lbs 

1296

21007585 

0-47871-07585-0 

100-47871-07585-7 

Cut Case (4 units) 

7.94 x 13.38 x 11.75 

2 lbs 

390

21007588 

0-47871-07588-1 

100-47871-07588-8 

Bulk Pack (4 units) 

6.5 x 9 x 6.5 

2 lbs 

720

21007583 

0-47871-07583-6 

100-47871-07583-3 

Cut Case (6 units) 

 6.63 x 13.25 x 6.25 

3 lbs  

1008

Not for sale by individual unit

120V AC Wire-In Smoke Alarm

Slide Load Front Battery Door

Model i4618

Technical Specifications

Model: 

i4618

UPC: 

0-47871-07581-2

Power Source: 

120VAC (

80mA Max)

Sensor: 

Ionization

Audio Alarm: 

85dB at 10ft

Temperature Range:  40˚F (4.4˚C) to 100˚F (37.8˚C)
Humidity Range: 

Up to 85% relative humidity (RH)

Size: 

5.6” in diameter x 1.8” depth

Weight: 

.5lbs

Interconnects: 

Up to 24 Kidde devices

LED: 

Green, receiving ac power

 

Red, 4 modes of operation

Warranty: 

5 year limited

Installation of Smoke Alarm

The smoke alarm should be installed to comply with all local codes having jurisdiction in your area, 

Article 760 of the National Electric Code, and NFPA 72. Make certain all alarms are wired to a single, 

continuous (non-switched) power line, which is not protected by a ground fault interrupter. A maxi-

mum of 1000 ft. of wire can be used in the interconnect system. Use standard UL listed household 

wire as required by code.

Model i4618

1016 Corporate Park Drive
Mebane NC 27302
1-800-880-6788
www.Kidde.com

Distributed by:

P/N: KL-i4618 sheet 

rev. 12-2009