TM0048
LaserNET Program User's Guide
September 2003
6-16
2. The time and date currently programmed in and the Detector is shown in the window. Time is shown in
a 24-hour format, HH:MM:SS. Date is in month-day-year order, MM-DD-YYYY. The time and date, if
incorrect, can be changed by highlighting the appropriate field and entering the correct number.
3. Select
<OK>
to save this configuration.
6-5.12
Factory Defaults
All settings can be returned to their factory defaults. These settings are shown in Table 6-1. All settings will
be returned to the default values simultaneously using the following procedure.
1. Select
Options>Configure>Factory Defaults.
The Default Configuration window will open, as shown
in Figure 6-18.
Figure 6-18. Default Configuration Window
2. To reset all parameters to their default values, select
<OK>
The configuration will be returned to default.
6-6
TEST OPTIONS
The following detector tests can be initiated from the Test Options menu. The detector sensitivity test is the
only required test for commissioning and maintenance procedures. Airflow Test, Trouble Relay Test and
Monitored Input Test are included to aid in troubleshooting the detector. See Chapter 7 and 8.
6-6.1
Sensitivity Test
A Detector sensitivity test can be run from the computer. It takes about 30 seconds to complete. The signal
averaging and referencing functions are disabled during the test.
1. Select
Options
>
Sensitivity Test
. If the Detector is working correctly, the smoke level bar graph on the
display and control graphic will rise to 75%. The display and control graphic will show "Test".
2. At the successful completion of the test, a "Test Pass" message as shown in Figure 6-19 will appear in
the Status box. Select
<OK>
to close the window.
Figure 6-19. Sensitivity Test Window
Summary of Contents for HART XL
Page 2: ......
Page 4: ...THIS PAGE INTENTIONALLY LEFT BLANK...
Page 6: ...ii September 2003 TM0048 LaserNET Program User s Guide THIS PAGE INTENTIONALLY LEFT BLANK...
Page 18: ...1 6 September 2003 TM0048 LaserNET Program User s Guide THIS PAGE INTENTIONALLY LEFT BLANK...
Page 28: ...3 6 LaserNET Program User s Guide September 2003 TM0048 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 60: ...TM0048 LaserNET Program User s Guide September 2003 6 22 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 75: ......