![background image](http://html1.mh-extra.com/html/kidde/fyrnetics-423-9hir/fyrnetics-423-9hir_installers-manual_1965065003.webp)
To avoid causing damage to the unit, to provide optimum performance, and to
prevent unnecessary nuisance alarms.
Do not install in bathrooms, garages or boiler rooms or anywhere that
may expose the sensor to substances that could damage or contami-
nate it.
Do not install in areas where the temperature is colder than 4.4
º
C
(40
º
F) or hotter than 37.8
º
C (100
º
F) such as attics, porches and
garages.
Near vents, flues, chimneys or any forced/unforced air ventilation
openings.
Near ceiling fans, doors, windows or areas directly exposed to the
weather.
In dead air spaces, such as peaks of vaulted ceilings or gabled roofs,
where carbon monoxide may not reach the sensor in time to provide
early warning.
Do not site within 1.8m of a fuel burning appliance
Do not site within 1.8m of a steam/moisture source e.g. bathroom,
garage or above a kitchen sink.
Do not site within 1m of dimmer control cabling.
Do not site within 1.5m of any light fixture or adjacent to a heat
source e.g. directly above a cooker.
In areas of humidity below 5% + above 95% (non-condensing).
In very dusty, greasy, or dirty areas e.g. boiler rooms.
Any location where the free flow of air to the alarm’s vents could be
interrupted (e.g. behind curtains/furniture).
Areas where routine maintenance or operating test/reset button is dif-
ficult (e.g. top of stairwells).
3. Where not to install your alarm
3
4. Installing the Alarm
• These are mains powered alarms, so isolate the mains supply before
commencing installation.
They are for installation by a qualified electri-
cian in accordance with the current I.E.E. regulations
(See section 7 if
interconnecting additional alarms).
• Select suitable location having regard to earlier advice.
• Bring house wiring through a dry lining box or Kidde surface pattress,
(SMK 23) into terminal block (not included).
• If wall mounting, connect supply through a 3 amp fused spur into
Kidde surface pattress SMK 23.
• Site the alarm at least 1.5m above the floor. When sited in same
room as an appliance, the alarm should be sited no closer than 1.8m
from the appliance.
• The appropriate power source is 230V AC power supply from a non-
switchable circuit, which is not protected by a ground fault interupter.
• When alarms are interconnected, all interconnected must be
SMK 23
BASE
PLATE
At least
1.5m above
floor
Ceiling Mounted
Wall Mounted
2512-7205-01.qxd:_ 2008.4.1 2:05 PM Page 3