6-15
July 2004
Argonite
®
Engineered Fire Suppression System
38-KFSARG-000
6-7.2
Orifice Plate Restrictor Assemblies
For large systems with 2-1/2, 3, or 4 inch pipe, use a Class 1500# flange. Only the orifice
plate will be provided by Kidde Fire Systems. The flange nuts must be torqued to at least the
minimum required by the flange manufacturer. See Figure 6-18 and Table 6-10.
ORIFICE PLATE RESTRICTOR
(P/N’S IN TABLE PROVIDE
ONLY THIS COMPONENT)
NUT *
GASKET *
CLASS 1500#
FLANGE *
BOLT *
* PROVIDED BY
INSTALLER
FLOW
Figure 6-18. Flanged Restrictor Assembly
Table 6-10. Flange Restrictor Assembly Details
Part Number
Description
38-250001-XXX
2½ in. Orifice Plate Restrictor, Code 13.5 to 35.0
38-300001-XXX
3 in. Orifice Plate Restrictor, Code 18.0 to 43.0
38-400001-XXX
4 in. Orifice Plate Restrictor, Code 25.0 to 56.0
Note: When ordering, specify an 11-digit hypenated part number; the flanged orifice plate restrictor part number plus the
three-digit orifice code (e.g., 38-300001-240 to order a 3 in. flanged orifice plate, orifice code 24.0).