Intrinsically Safe (IS) Products

ATEX 94/9/EC

and IECEx

Installation Guide

 

General

All Apollo IS devices are intended for use in hazardous area systems complying with the 

European ATEX directive 94/9/EC that deals with products used in hazardous areas. All such 

systems must incorporate a certi

fi

 ed safety barrier or interface to limit the voltage and power 

to the circuit. Information on suitable barriers and interfaces can be obtained from Apollo.

These notes are intended to supplement the mandatory requirements of the ATEX directive or 

other applicable regulations They should not be taken as full instructions for the design and 

installation of intrinsically safe systems. These activities must be carried out only by quali

fi

 ed 

personnel.

Certifi cation

The XP95 IS range of detectors and manual call points (MCPs) and the Orbis IS range of 

detectors are BASEEFA certi

fi

 ed as components. Their component certi

fi

 cation allows them to 

be used in certi

fi

 ed intrinsically safe systems.

Each product range is covered by a system certi

fi

 cate issued by BASEEFA in Apollo’s name. 

Systems installed according to Apollo system drawings will be covered by the system 

certi

fi

 cation. The use of barriers, interfaces, or other components not included in the system 

drawing will invalidate the certi

fi

 cation. 

The system certi

fi

 cate number must be marked on the installed system, preferably on the 

barrier or interface housing. The system is certi

fi

 ed to ATEX only.