background image

 IOCB1616 Installation Guide (Aurora 06.15) 

Notes 

When an “Input Time Zone Assignment” is used, the input remains shunted and does not 
notify the software regardless of the change of input state when a time zone is turned on. 
When an “Output Time Zone Assignment” is used, the output remains in a normal state 
when the time zone is on regardless of the input trigger. 
Restoring associated inputs to normal resets the output state to normal. 

Global Inputs & Outputs 

The following modes – Optional I/O Delayed Output, Optional I/O Timed Output and 
Optional I/O Pulsed Output – are reserved for global inputs/outputs when used with the 
IOCB1616. Refer to the Aurora Global Inputs and Outputs / Schedules on the Keyscan 
Product Documentation Library CD.  

Examples of IOCB1616 Modes 

01 – Delayed Output 

Example: Freezer Door – Need to know immediately that the freezer door is open and if 
the door remains open after a specified time an alarm sounds. 

Input 1 is defined as the freezer door; Output 1 is defined as the freezer siren. Opening the 
freezer door trips Input 1 sending an alarm notification to the guard's computer. If the 
door remains open passed Output 1's specified delay time, the freezer siren is triggered 

notifying the client that the freezer door has been left open. The siren remains active until 
the freezer door is closed. 

02 – Timed Output 

Example: Lights – Turn the lights on in a computer room as soon as motion is detected. 

Input 2 is defined as the computer room motion detector; Output 2 is defined as the 
computer room lights. As soon as motion is detected in the room, Output 2 is triggered and 
remains active for the duration of Output 2's specified time. If motion is still detected the 
output remains active until the device does not sense movement. 

03 – Pulsed Output 

Example: Notification – Warehouse notification when a truck arrives at the shipping dock. 

Input 3 is defined as the shipping dock; Output 3 is defined as shipping dock strobe/siren. 

When a truck arrives at the shipping dock you can manually trigger Input 3 via a push 
button which will then pulse the strobe/siren for the duration of the specified output time. 

04 – Input/RTE 

Example: Automated Unlock at Exit Door – Control the exit point of a door without the use 
of an access control reader. 

Input 4 is defined as the side door RTE (Request to Exit); Input 5 is defined as the Door 
Contact, Output 4 is defined as the door lock hardware. As the person walks towards the 
door, the RTE device will detect the individual; Output 4 will unlock the door hardware; 
Input 5 will shunt the door contact for the duration of the specified output time and allow 
the individual to exit without creating an alarm. (Input 4 must be triggered before Input 5; 
otherwise Input 5 reports an alarm in the Client software.) 

05 – Delayed Input & Delayed Output 

Example: Monitoring – Monitor a low security stairwell door. 

Input 5 is defined as the stairwell door; Output 5 is defined as the stairwell door strobe. If 
the stairwell door is opened, the alarm notification to the guard’s computer is delayed by 
the specified input delay time. Output 5 will not activate the strobe until the end of the 
cumulative input and output times have expired. The strobe stops when the input is 
secured. 

Summary of Contents for Aurora IOCB1616

Page 1: ...may be employed Monitor door inputs and use request to exit devices without a reader assignment and trigger a sounder such as a siren or a sound alert Trigger an auxiliary third party product such as...

Page 2: ...he door contact is left open after the associated input time has expired 05 Delayed Input Delayed Output If the input is triggered the alarm is delayed The input is delayed by the specified input time...

Page 3: ...puter room lights As soon as motion is detected in the room Output 2 is triggered and remains active for the duration of Output 2 s specified time If motion is still detected the output remains active...

Page 4: ...tion when multiple inputs are assigned to a common output any one input fires the output And Condition With the AND condition when two multiple points are assigned to any common output both points nee...

Page 5: ...n the site in the Hardware Setup directory screen 2 From the Hardware Setup screen double click on the control unit that is connected to the IOCB1616 in the All Hardware screen 3 Select the IOCB1616 t...

Page 6: ...OCB Output 1 or the first output to be named 3 In the text box enter a name or description appropriate for the output 4 If you are applying a delay for this output double click on the output under the...

Page 7: ...and the row with the default Input Output is not applicable set the Mode column for that row to Not Used The following table illustrates an example where the default Input 3 is not assigned to Output...

Page 8: ...tting on Not Used If you make an error or need to clear the assignment select Clear Operator and Secondary Input 4 Under the Secondary Input column double click on the highlighted row and choose the d...

Page 9: ...ect the IOCB Devices tab 3 Below the IOCB Inputs heading click in the box to the left of the access control unit IOCB Input The box has an x when selected If you are assigning multiple IOCB inputs to...

Page 10: ...same schedule click in the box of each applicable output The box has an x when selected 4 Click on the symbol to the right of Schedule and select the schedule from the drop down list 5 Click on the As...

Page 11: ...e 1 reviews the Input Output assignments and table reviews the input supervision selections Jumper Off Off 0 Jumper On On 1 5 4 3 2 1 J17 Jumper Settings Jumper Pins KI 00387E 10 11 J17 Jumper Setting...

Page 12: ...able IOCB1616 function for PC1097 or later control boards is set in the Aurora software from the Hardware Setup Additional Settings screen under the Hardware Settings heading To enable the control boa...

Page 13: ...in Standoffs Cover Locking Screw Cover Locking Screw Cover Locking Screw Cover Locking Screw Alternate Locations for Optional OCB 8s KI 00388E 10 11 Dual IOCB1616 Circuit Boards Front View Cover not s...

Page 14: ...J11 J12 J13 J14 J15 J16 H1 H2 Max Current 400 mA Normal Reversed 1 to 8 9 to 16 Input Output Control Board Short J18 on last IOCB only PROM Ver RX TX Gnd 12V AUX POWER Supervised Inputs 1 2 3 4 5 6 16...

Page 15: ...Lock power and ACU power must be separate supplies Current consumption without low current open collector connected to any device draws 100mA RX TX GND 12V AUX Power IOCB1616 Circuit Board Red Power C...

Page 16: ...n without low current open collector connected to any device draws 100mA OCB 8 GND 12V J9 Ext Pwr ACU Pwr OCB 8 GND 12V J9 Ext Pwr ACU Pwr Set J9 jumper to Ext Pwr Set J9 jumper to Ext Pwr Second side...

Page 17: ...n with ACU RX TX GND 12V AUX Power IOCB1616 Circuit Board 1 RX TX GND 12V AUX Power IOCB1616 Circuit Board 2 RX TX RX RX TX TX Refer to the Keyscan Technical Guide for ACU to PC communication ACU Circ...

Page 18: ...4 5 6 16 15 14 13 12 High Current Open Collector Control Points 2 Amp Max 16 1 Normally Closed Contact Jumper 4 Off 1 Input 1 Door Contact 1 Input 1 Door Contact to Common Return Normally Closed Cont...

Page 19: ...IOCB1616 PROM Ver RX TX Gnd 12V AUX POWER 2 3 4 5 6 16 15 14 13 12 High Current Open Collector Control Points 2 Amp Max 16 Supervised Inputs 12 VDC Strike 12 VDC Lock Power Auxiliary output device sw...

Page 20: ...tput 05 Relay 06 Output 06 Relay 07 Output 07 Relay 08 Output 08 Relay 09 Output 09 Relay 10 Output 10 Relay 11 Output 11 Relay 12 Output 12 Relay 13 Output 13 Relay 14 Output 14 Relay 15 Output 15 Re...

Page 21: ...This page is intentionally blank...

Page 22: ...Keyscan Inc A Member of the Kaba Group 22 This page is intentionally blank...

Page 23: ...IOCB1616 Installation Guide Aurora 06 15 23 This page is intentionally blank...

Page 24: ...4 Keyscan Inc 901 Burns St E Whitby Ontario Canada L1N 0E6 1 888 539 7226 toll free Canada USA 905 430 7226 elsewhere www keyscan ca Technical support hours 9 00 A M to 6 30 P M Eastern Time IOCB1616...

Reviews: