Table 1 contains the list of all parameters of the user. The first column includes
examples of display indications, the next columns: description of a given parameter,
minimum and maximum set value, jump of the value while being set and the last
column contains the default values set by the producer. They can be restored by
selecting the service function [Prod].
Table 1. List of parameters of the user.
Display
Parameter
Min Max Jump
Default
setings
c50°
Temperature of water in central heating circulation
-15°
Outside temperature
d-10
Value of installation water temperature decrease
-30
0
1°C -10
co C
Manual
switching
between
working
modes
(WINTER/SUMMER) of the unit
C
-
C
LL10 Threshold temperature WINTER
0
30
1°C
10
LH18 Threshold temperature SUMMER
0
30
1°C
18
E ??
Temperature sensors alarms damage
3.1 Temperature of water in central heating circulation [c50°].
The parameter enables the user to view the measured water temperature of the
central heating system. In order to display the programmed temperature of the central
heating system (the temperature that the regulator is aiming at), press and hold the
OK button. This is signalized by flashing of the first LED on the display e.g. [c.50°].
The regulator returnes to this basic parameter automatically after 60 seconds. This
means the regulator will switch to displaying water temperature of the central heating
circulation when e.g. the user switches to viewing the outside temperature and during
the period of 60 seconds will press no button at all. The exception to the rule are
emergency situations. In such cases, the default alarm is displayed.
3.2 Outside temperature [-15°].
This parameter shows the outside temperature. If the desired temperature of
installation water is counted on the basis of the average outside temperature, press
and hold the OK button to find out the current average outside temperature, e.g.
[A.-10].
3.3 The rate of installation water temperature decrease [d-10].
The value set in this parameter determines by how many degrees the temperature of
the installation water in the central heating system will be decreased in the case of
opening contacts of nighttime temperature decrease input. This is calculated on the
weather characteristics.
In order to change the parameter you need to press the OK button, while it is being
displayed. The regulator will switch into the edition mode, signalized by flashing digits
of the parameter being changed. By pressing (+,-) buttons, you need to set the desired
level of temperature and confirm your choice with the OK button. Pressing the (*)
button will cause cancellation of the introduced change and exiting the edition mode.
Also, the cancellation of changes will occur, if the parameter will not be confirmed
during 60 seconds since the last change