1. Application.

The UMS-4PS weather compensating controller is a microprocessor device designed

for weather compensating central heating temperature control in the installations

powered by a central heating system. The temperature in the central heating

circulation is maintained by controlling the servomotor of the mixing valve.

The controller is equipped with the output designed for controlling the central heating

pump, the temperature of installation water decrease input and the heating turn-off

input. The construction of the device makes it possible to connect parallelly any given

number of UMS-4PS controllers which means that one boiler or central unit may be

connected independently to many central heating systems.

2. Connection.

Before turning the power on, the cables powering the controller, the servomotor of the

mixing valve and the cables powering the central heating pump should be connected

to the appropriate sockets. The outside temperature sensor may be connected

parallelly to any given number of UMS/UMP controllers, bearing in mind that

appropriate contacts should be connected to the suitable contacts of the controller.

Each UMS-4PS controller requires a separate central heating temperature sensor.

Detailed connection scheme is presented in the picture 3.

CAUTION!

Before plugging in the controller make sure that the wiring system is

properly grounded.

3. Operation.

The front panel of the controller (picture 1) contains:

1 – Display.

2 – Servomotor of the mixing valve indicator (opening).

3 – Servomotor of the mixing valve indicator (closing).

4 – temperature sensors and additional features control inputs connector

5 – (-) button used for selecting and changing parameters.

6 – OK button used for changing and accepting parameters.

7 – (+) button used for selecting and changing parameters.

8 – (*) button.

9 – central heating pump control connector.

10 – central heating pump control input indicator.

11 – power and the mixing valve servomotor control connector.

Summary of Contents for UMS-4PS

Page 1: ...OPERATION MANUAL UMS 4PS UNIVERSAL WEATHER COMPENSATING CONTROLLER Version HC22...

Page 2: ......

Page 3: ...ral heating pump should be connected to the appropriate sockets The outside temperature sensor may be connected parallelly to any given number of UMS UMP controllers bearing in mind that appropriate c...

Page 4: ...e controller is in the WINTER mode In this mode the task of the controller is to maintain an appropriate temperature in the central heating system The temperature depends on the outside temperature or...

Page 5: ...eans the regulator will switch to displaying water temperature of the central heating circulation when e g the user switches to viewing the outside temperature and during the period of 60 seconds will...

Page 6: ...itch between the modes can be made manually 3 6 Temperature sensors damage The regulator tests functioning of measuring channels continually In case of detecting a damage the coded alarm is displayed...

Page 7: ...9 9 1 C 0 cL20 The minimum temperature of heating circuit water 5 60 1 C 20 cH75 The maximum temperature of central heating circulation 40 90 1 C 75 ch 2 Mixing valve servomotor work hysteresis 1 9 1...

Page 8: ...les the user to set the adequate inclination and change the weather characteristics The relation between the outside temperature or averaged outside temperature the set parameters and the programmed w...

Page 9: ...alue set in this parameter Protection from excessive increase of central heating circulation temperature is of considerable significance in case of underfloor heating where the temperature should not...

Page 10: ...ased upon the weather chara cteristics Changing the parameter to n results in the current outside temperature which is used to calculate the programmed installation water temperature CAUTION The memor...

Page 11: ...Installation water temperature decrease input shall not be connected to any other UMP UMS inputs directly 5 2 Central heating turn off input Closing 7 8 contacts of UMS 4PS unit will turn off the cen...

Page 12: ...the outdoor temperature sensor d 10 Value of decrease in installation water temperature LL10 Threshold temperature WINTER LH18 Threshold temperature SUMMER cF40 The ratio of the weather characteristi...

Page 13: ...13 Picture 3 UMS 4PS controller and boiler configuration scheme...

Page 14: ...14...

Page 15: ...06 BS EN 61000 3 2 2007 EN 61000 3 3 2008 BS EN 61000 3 3 2011 Information on disposal This appliance is marked according to the European Directive 2002 96 EC on Waste Electrical and Electronic Equipm...

Page 16: ...Manufacturer P W KEY 11 200 Bartoszyce ul Bohater w Warszawy 67 tel 89 763 50 50 fax 89 763 50 51 www pwkey pl e mail pwkey onet pl...

Reviews: