25
Minimum operating time without cleaning
- the parameter is available only when
the cleaning mechanism operates in the AUTO or COMBI mode. It specifies the
minimum number of hours the burner must operate so that the cleaning could be
activated. If the minimum operation time is not reached, the cleaning will not be
started even if the required number of shutdowns has occurred. To turn off the
„Minimum operating time without cleaning' option, set the parameter to „0h'.
M I N W O R K W I T H O U T
C L E A N I N G
2 h
Maximum operating time without cleaning
- the parameter is available only when
the cleaning mechanism operates in the AUTO or COMBI mode. It specifies the
maximum number of hours the burner can work without cleaning. If the maximum
time is reached, the cleaning will be started even if the required number of
shutdowns has not occurred.
M A X W O R K W I T H O U T
C L E A N I N G
1 2 h
5.5. Central heating pump work parameters.
Central heating pump switching on parameters
- this parameter specifies the
method of central heating pump switching on. Selection of „THERMOSTAT” setting
means that central heating pump will be switched on only if room thermostat
contacts are closed and in case of emergency (e.g. boiler overheating). Selection of
„AUTO” setting means that central heating pump operation will follow regardless of
room thermostat.
C H P U M P W O R K
M O D E
A U T O
Central heating (CH) pump periodic switching on
- this parameter enables
periodic operation of central heating pump and water transfer in the heating circuit.
The pump is activated periodically every 30 seconds according to selected time in
„CH pump periodic work” setting. This function in available, if „THERMOSTAT” was
selected in CH pump work mode
C H P U M P
P E R I O D I C
W O R K
Y E S
CH pump periodic work time
- this parameter is available, if CH pump works in
„THERMOSTAT” mode and the function of CH pump periodic work is active. The
programmed setting will specify the time lapse between CH pump work, in case of
opened contacts of the room thermostat.
C H P U M P
P E R I O D I C
W O R K
T I M E
2 m i n