15
Burner start up counter.
Reading of this counter defines start number of the ignition attempts.
B U R N E R S T A R T
C O U N T
8
5. Settings – service mode.
Holding OK button for 3 seconds enters the service mode where you can review and
change the parameters by pressing the selection buttons (8 and 11). After selection
of the given parameter you can enter into the change mode with OK button that is
indicated by the displayed symbol „→” on the left of the desired parameter. Pressing
OK button will confirm the change. If you press STOP button changes will not be
saved and old settings will be resumed. If the device is in change mode or
parameters reviewing for 60 seconds, the controller will automatically go back to the
display mode. Table 3 presents the list of all service settings. Columns of the table
represent: flashing light, parameter name and available minimum and maximum
setting.
Table 3. Service settings.
Light
Parameter
Min.
Max.
No
Language selection (See description).
Fan
Fan modulation during boiler start.
NO
YES
Min. fan speed during heating up.
1%
100%
Max. fan speed during heating up.
1%
100%
Ignition modulation start delay.
0s
250s
Fan speed during ignition.
1%
100%
Fan speed at max. power.
1%
100%
Fan speed at min. power.
1%
100%
Fan speed at extinction.
1%
100%
Fan speed during cleaning mode.
0%
100%
Fan scavenge (air purging).
NO
YES
Fan scavenge (air purging) blow time.
5s
60s
Fan scavenge (air purging) pause time.
1min
99min
Fan speed during scavenge.
1%
100%
Auger
Auger filling time.
1min
99min
Initial fuel feed.
0s
250s
Fuel feed cycle.
1s
250s
Fuel feed during ignition.
0%
100%
Fuel feed for max burner power.
1%
100%
Fuel feed for min. burner power.
1%
100%
Stoker work mode (See description).
Stoker work time.
1s
99s
Stoker pause time.
1s
99s
Stoker extra work time.
1s
99s
Stoker emptying time.
1s
99s
Auger ignition test.
NO
YES
Auger ignition temperature.
20°C
99°C
Igniter
Flame detector type (See description).
Correction FD-1.
0
99
Hysteresis loss of flame (optical sensor).
1
255