KEY RK-2006LP Operating Manual Download Page 1

OPERATING MANUAL

RK-2006LP

AUGER FITTED SOLID FUEL

BOILER TEMPERATURE CONTROLLER

Version DC19

Summary of Contents for RK-2006LP

Page 1: ...OPERATING MANUAL RK 2006LP AUGER FITTED SOLID FUEL BOILER TEMPERATURE CONTROLLER Version DC19...

Page 2: ......

Page 3: ...cations that shall be dry Figure 2 presents the electrical connection diagram For connection of stoker alarm indicator and ash removal system the additional module UM 1 shall be applied CAUTION Before...

Page 4: ...here is 1 Display 2 Fan indicator 3 Auger indicator 4 Ignition glow plug indicator 5 Central heating circuit pump indicator 6 Hot tap water pump or mixing pump indicator 7 Room thermostat operation an...

Page 5: ...e boiler To do this turn the boiler thermostat knob 12 according to the desired setting and confirm with OK button Press the knob D E S I R E D B O I L E R T E M P E R A T U R E 5 8 c CAUTION When the...

Page 6: ...c water pumps operation but automatic ignition does not follow AUGER EXTINCT EMERGENCY SHUTDOWN Fuel ignition in auger channel The controller empties ignited fuel from the auger channel until temperat...

Page 7: ...OPERATION MODE When in this mode the controller operates fuel auger and fan to ensure max power of the boiler Fuel and air feeding rate is adjusted by the technician Pressing STOP button exceeding ti...

Page 8: ...nace cleaning is carried out if the extinction time has been determined by the technician or the burner has been operating long enough In the mode the cleaning mechanism is activated for the period pr...

Page 9: ...s by pressing START button A L A RM O U T O F F U E L EMERGENCY ALARM Depending on construction type the boiler may be equipped with emergency sensor e g hopper cover sensor Activation of the alarm wi...

Page 10: ...ncreases above 93 C it will activate STB system which will automatically engage power for central heating pump and will shut off blower Operation of STB will result in switching the controller to STAN...

Page 11: ...omatically if repairs are made 4 Review of user settings Pressing parameter buttons 8 and 11 allows reviewing user s parameters while their activation is indicated with fast flashing of proper light F...

Page 12: ...rk time Burner start up counter 4 1 Fuel type selection RK 2006LP controller enables programming ignition settings for four different fuel types Fuel type parameter enables switching between particula...

Page 13: ...n follow at the same time H O T W A T E R P R I O R I T Y N O Bacterial flora liquidation in domestic water tank the controller enables manual activation of program for bacterial flora liquidation in...

Page 14: ...ion of the temperature detector of burner fuel ignition If the system is fitted with optical fire burner detector parameters change and viewing is unavailable Burner measured temperature this paramete...

Page 15: ...setting Table 3 Service settings Light Parameter Min Max No Language selection See description Fan Fan modulation during boiler start NO YES Min fan speed during heating up 1 100 Max fan speed during...

Page 16: ...mp Domestic water path See description Domestic water heating hysteresis 1 C 20 C Boiler increase temperature during hot tap water heating 2 C 20 C Domestic pump work extension NO YES Domestic pump wo...

Page 17: ...er start M A X F A N S P E E D H E A T I N G U P 6 0 Ignition modulation start delay this parameter is available if the function of fan modulation during boiler start is selected and it describes oper...

Page 18: ...rging which simply includes periodical switching on of the fan during burner operation for the purpose of removal of accumulated gases F A N S C A V E N G E Y E S Fan scavenge air purging blow time th...

Page 19: ...during ignition this parameter specifies fuel dose that is fed to the burner during lighter operation The programmed setting specifies feeding time in percent in relation to the time of whole work cy...

Page 20: ...s switched off or in automatic mode S T O K E R P A U S E T I M E 3 s Stoker extra work time this parameter is available only when the stoker works in automatic mode and it specifies stoker work time...

Page 21: ...lame brightness measurement FD 1 optical detector shall be used F L A M E D E T E C T O R F D 1 Correction of the photodetector indications the parameter is available only when an optical flame detect...

Page 22: ...with adequate message displayed on the display To start the controller first refill the fuel then cancel by pressing STOP button and start setting mode by pressing START button I G N I T I O N T R Y...

Page 23: ...and is activated when the determined number of shutdowns or long burner working time occurs The automatic cleaning depends on the furnace extinction starting the cleaning mechanism for the period set...

Page 24: ...the period between the mechanism successive turn ons M E C H A N I S M P A U S E T I M E 1 2 0 s Cleaning mechanism opening time the parameter is available only when the cleaning mechanism operates i...

Page 25: ...ral heating pump switching on parameters this parameter specifies the method of central heating pump switching on Selection of THERMOSTAT setting means that central heating pump will be switched on on...

Page 26: ...in the tank in relation to the programmed setting so that charge pump was switched on This setting is available if domestic water path EXISTS setting was selected H W H E A T I N G H Y S T E R E S I...

Page 27: ...e burner extinction because the boiler upper hysteresis would be exceeded The parameter defines the time required to stabilize the circulation after heating the DHW with priority on has finished Durin...

Page 28: ...burner extinction shut down B O I L E R U P P E R H Y S T E R E S I S 5 c Burner power switching hysteresis when the programmed boiler water temperature is obtained the controller is switched to mini...

Page 29: ...ed the lamp will be off CAUTION The room thermostat input is active during work in the WINTER mode only The indicator signalizing the status of the input is independent of the entered mode Room thermo...

Page 30: ...guished immediately after the thermostat contacts have been opened B U R N E R S W I T C H O F F D E L A Y 0 m i n CAUTION The burner may be turned off after the thermostat contacts have been opened w...

Page 31: ...overheating or lack of fuel 7 Controller disassembly If controller disassembly is necessary follow the following procedure Disconnect the boiler and controller from power supply Remove the controller...

Page 32: ...32 Figure 2 RK 2006LP Controller connection diagram...

Page 33: ...ettings 1 2 3 4 Thermostat Boiler max power HTW pump Domestic water desired temperature Domestic water heating priority Igniter Brightness when fuel ignition has occurred FD 1 Burner temperature with...

Page 34: ...avenge air purging pause time Fan speed during scavenge Auger Auger filling time Initial fuel feed Fuel feed cycle Fuel feed during ignition Fuel feed for max burner power Fuel feed for min burner pow...

Page 35: ...ting pump periodic work Central heating pump periodic work time HTW pump Domestic water path Domestic water heating hysteresis Boiler increase temperature during hot tap water heating Domestic pump wo...

Page 36: ...36...

Page 37: ...37...

Page 38: ...38...

Page 39: ...0 4 11 2005 U PN EN 60730 1 2002 A1 2006 U A12 2004 A13 2005 PN EN 60730 1 2005 A14 2006 PN EN 60730 2 9 2006 PN EN 61000 3 2 2006 U PN EN 61000 3 3 1997 A1 2005 A2 2006 IS1 2006 Information on dispos...

Page 40: ...Manufacturer Przedsi biorstwo Wielobran owe KEY 11 200 Bartoszyce ul Bohater w Warszawy 67 tel 89 763 50 50 fax 89 763 50 51 www pwkey pl e mail pwkey onet pl...

Reviews: