Serial IR & IR Emitter Control

 

½

The “Serial IR” port requires the use of a Male 3.5mm Mono cable (not included) with the IR 
command signal being carried on the “Tip” of the input inserted into the KD-HDSW unit.  The 
location of the IR signal may vary by control system used.  Please verify the location of the IR 
signal with your control system.

 

½

When using the IR Emitter / IR Extender (sold separately), the 
IR Emitter must be mounted over the IR Sensor on the KD-
HDSW unit.  It is recommended that the rear IR sensor of the 
KD-HDSW unit be utilized for these applications. One end of 
the cable is connected to the IR Receiver / Master Controller 
/ IR Extender / IR Connecting Block, while the other end is 
mounted over the IR Sensor of the KD-HDSW unit.

RS-232 Commands and Protocol

 

½

KD-HDSW units are compatible with all Control Systems, such as AMX

®

, Control4

®

, Crestron

®

RTI

®

, Universal

®

 

½

Connect your Control System’s Master Controller to the KD-HDSW unit using the RS-232 port.  
Follow all instructions provided with your control system.

 

½

RS-232 Protocol:

 

»

Baud Rate = 9600 bits per second

 

»

Data Bits = 8

 

»

Parity = None

 

»

Stop Bits = 1

 

»

Flow Control = None

RS-232 Command List:

RS-232 Command

Description

Comments

pwr_1

Power On

pwr_0

Power Off

sel_x

x = 1-4, 5, 6

1-4 = Input #, 5 = Up, 6 = Down

asl

Auto Select Enable/
Disable

hep

Help

Full RS-232 command listing

sta

Status

“s1y” y = active input

sir_x_x_y

Addressing per 
Command

x x = desired two-digit address for 
command (01 – 99) 
y = Input Select, Up, Down (1-4, 5, 6)

gir

Address Setting Status

dir_y

Delete Address Setting 
per Command

y = Input Select, Up, Down (1-4, 5, 6)

 

½

All RS-232 commands must be in lower case letters, require spaces where indicated above with 
( _ ), and require a carriage return to be sent.

Multiple KD-HDSW Unit Configurations

Up to 99 individually addressable units can be installed.  KD-HDSW switchers allow you to assign 
a two-digit address to each unit or each of the selectable inputs.  This capability can be configured 
via IR or the RS-232 port.

 

½

Addressing Buttons / Units via IR

 

»

With power enabled on the unit, press the “Power On” button.  The “Input Select” LED 
lights will begin to blink, indicating that the KD-HDSW unit is ready to receive the address 
information.

 

»

Press the first digit (0 – 9) of the two-digit address.  Once this first digit has been received 
“Input Select 1” LED will blink.  

 

»

Press the second digit (0 – 9) of the two-digit address.  Once this second digit has been 
received “Input Select 1” and “Input Select 2” LED’s will blink.

 

»

Press the Input Select button (Input 1 – Input 4, Up or Down) that you wish to assign the 
two-digit address to.  Once this is completed, all “Input Select” lights will become solid 
indicating that the Input Select button has now been re-addressed.  

 

»

Repeat Steps 2 through 4 if you wish to assign an address to additional “Input Select” 
buttons or to your entire KD-HDSW unit.  

 

»

Press “Power On” button to exit addressing mode when completed.  

 

½

Addressing Buttons / Units via RS-232

 

»

See “RS-232 Commands and Protocol” section for RS-232 Addressing Commands

 

»

To address an Input, use “sir_x_x_y” command.  To address an entire unit, repeat command 
for each Input, Up, and Down

 

»

For address settings, use “gir” RS-232 command to receive a list of address settings

 

»

To delete address settings, issue “dir_y” RS-232 command

Ground

Signal

KD-HDSW_Series_Manual_2011.indd   4-5

8/2/11   12:44 AM