RS-232 and TCP/IP Commands

KD-Pro8x8D allows control over serial interface for bi-directional communication.  
Use pins 3, 4, 5 for RS-232 communication.
In addition to RS-232, the serial interface may also be accessed using a TCP/IP connection 

 

»

Default IP address is 192.168.1.239, with default port 23

Connection Protocol:

 

»

Baud Rate = 57,600 bits per second

 

»

Data Bits = 8 

 

»

Stop Bits = 1

 

»

Parity = None

 

»

Flow Control = None

 

»

Carriage Return: Required

Notes

 

»

Commands are not case-sensitive

 

»

Spaces are shown for clarity; commands should NOT have any spaces

 

»

After a new command is received, a prompt should be sent back

Response from Help command

 – Returns entire API in readable format:

KD-Pro8x8D> H

-------------------------------------------------------------------------

--                     Key Digital Systems  HELP                       --

-------------------------------------------------------------------------

--        KD-Pro8x8D                             F/W Version : 1.03    --

-- System Address : 00                                                 --

--                                                                     --

-- Azz      : All Commands may have Prefix System Address zz=[01-99]   --

-- H        : Help                                                     --

-- PHO      : Help for Output Setup Commands                           --

-- PHE      : Help for EDID Setup Commands                             --

-- PHC      : Help for Control I/O Setup Commands                      --

-- PHT      : Help for Status Commands                                 --

-- PF       : Power Off                                                --

-- PN       : Power ON                                                 --

--                                                                     --

-- SPC A xx      : Set System Address, xx = [00-99] (00=Single)        --

-- SPC CM x      : Set System Command Mode, x = [0-9]                  --

-- SPC UM x      : Set System User Mode, x = [0-1]                     --

-- SPC FB E/D/T  : Front Panel Buttons Enabled/Disabled/Toggle         --

-- SPC BIRS z    : IR Source, z = [1-3] (1-Wired, 2-Sensor, 3-IR MIX)  --

-- SPC RSB z     : Set RS232 Baud Rate to z bps, z=[0-4]               --

--                 [0:57600, 1:38400, 2:19200, 3:9600, 4:4800]         --

-- SPC FAN z     : Set FAN Speed z [0:OFF, 1-8:SPEED LEVEL, 9:AUTO]    --

-- SPC DISP z    : Set Front Display(LED) z [0:OFF, 1:ON, 2:AUTO]      --

-- SPC TIME hh:mm:ss : Set Time by hh=[00~23], mm=[00~59], ss=[00~59]  --

Summary of Contents for KD-Pro8x8D

Page 1: ...d Audio DSP De embedding of Analog L R Balanced Unbalanced Digital Coaxial Audio ARC Includes 8 Rx Extenders 6 Short 2 Long Range KD Pro8x8D Operating Instructions The Experts in Digital Video Technol...

Page 2: ...Specifications 27 Important Product Warnings Safety Instructions 28 How to Contact Key Digital 29 Warranty Information 29 Introduction Key Digital KD Pro8x8D is a UHD 4K HDCP 2 2 and ARC supporting di...

Page 3: ...nd lip sync delay per output Long Range Mode Outputs 1 and 5 extend 1080p signals up to 500 ft 152m using CAT5e 6 Full Buffer Technology Full buffering of HDCP and EDID for the fastest possible switch...

Page 4: ...SHRx Up to 200 feet 1080p 60 1080p 24 1080i 720p Up to 125 feet 4K Ultra HD KD X88LGRx Up to 500 feet 1080p 60 Long Range Mode Up to 328 feet 1080p 60 Standard Range Mode Up to 328 feet 4K Ultra HD Lo...

Page 5: ...CA The audio de embed ports provide audio output of the selected HDMI input for the respective output default or returned audio ARC from the connected display if enabled See Audio Return Channel ARC s...

Page 6: ...PC Default IP address is 192 168 1 239 with default port 23 Firmware Mode Switch Should remain in Operation setting unless instructed by Key Digital technical support If changing position of switch d...

Page 7: ...input source for Control Routing RS 232 and TCP IP commands may be found in the RS 232 TCP IP Commands section Pin out Pin 1 IR Signal Pin 2 IR Ground Pin 3 RS 232 Tx Data Pin 4 RS 232 Ground Ping 5 R...

Page 8: ...rmost 1 2 7 8 are NOT illuminated Factory default reset is achieved by simultaneously holding the input select buttons 1 4 for 10 seconds The matrix reboots after reset The LEDs will ramp until reboot...

Page 9: ...S232 RS232 IR RS232 Main Huddle Mirrored Displays 1 8 HDMI RJ45 WiFi RJ45 HDMI IR Technical Support email tech keydigital com phone 914 667 9700 ext 3 www keydigital com compass Compass Control Pro Si...

Page 10: ...llation steps may be configured using the factory remote control Other advanced settings may be configured using USB and software downloaded from www keydigital com Matrix Switching Command via IR IR...

Page 11: ...XX IR Button Sequence R2 XX Treble ZZ Write EDID from Default EDID File ZZ to All Inputs IR Button Sequence R2 Treble ZZ Write EDID from Output YY to Input XX IR Button Sequence R2 XX Bass YY Write ED...

Page 12: ...R1 XX Lip Sync YY Set Output XX Audio Delay Up IR Button Sequence R1 XX Lip Sync Up Set Output XX Audio Delay Down IR Button Sequence R1 XX Lip Sync Down Set Output XX Audio Return Channel On IR Butto...

Page 13: ...ge to inform the device that a partner is always connected and active If set to Bypass Hot Plug Detection HPD voltage is bypassed from connected output display to the matrix Long Range Mode Extends 10...

Page 14: ...Range Rx unit HDBaseT F W Upgrade A HDMI Forced HPD ON Standard Rx unit HDBaseT F W Upgrade B HDMI Forced HPD ON Long Range Rx unit HDBaseT F W Upgrade C Optical Rx Bypass Standard Rx unit HDBaseT F...

Page 15: ...and analog audio connection will provide the audio returned from the display output ARC Support via HDBaseT Outputs 1 and 5 only Supported by KD X88LGRx only not KD X88SHRx KD X88LGRx supports ARC on...

Page 16: ...P12FM Company KEY 8x HDMI Outputs Use Key Digital s KD IQJUMP12FM sold separately jumper cable as the control breakout port Default setting control pass thru A simple pass thru of an IR or RS 232 sign...

Page 17: ...of control routing for control of devices connected via HDBaseT Rx units Third Party Control Processor RS 232 Unit control may also be TCP IP RS 232 Source to control all RS 232 devices IR Source to c...

Page 18: ...RSS 1 S yy xx RS 232 destination yy RS 232 source To configure the path of RS 232 control signals from an Control I O Port to an HDMI output use the command SPOH xx RSS 1 S yy xx RS 232 destination y...

Page 19: ...rical keypad for XX YY and Z values below Advanced unit setup should be completed in the KD Wizard software found on www keydigital com All unit setup should be completed in the KD Wizard software fou...

Page 20: ...ss to xxx xxx xxx xxx R3 Bass X X X Video Mode X X X Video Mode X X X Video Mode X X X Set Net Mask to xxx xxx xxx xxx R3 Middle X X X Video Mode X X X Video Mode X X X Video Mode X X X Set Router IP...

Page 21: ...urns entire API in readable format KD Pro8x8D H Key Digital Systems HELP KD Pro8x8D F W Version 1 03 System Address 00 Azz All Commands may have Prefix System Address zz 01 99 H Help PHO Help for Outp...

Page 22: ...mat by Auto Forced DVI BYPASS SPC ARC XX ON OFF Set ARC of HDMI Output xx to ON OFF Audio OUtput DSP Setup Command xx 01 08 A A All SPO xx AV yy Set Output xx Audio Volume to yy 00 99 U D SPO xx AB yy...

Page 23: ...Audio PCM DTS DOLBY HD DEFAULT EDID 04 HDMI Video 1080p 60 3D Audio 2CH PCM DEFAULT EDID 05 HDMI Video 1080p 60 3D Audio PCM DTS DOLBY DEFAULT EDID 06 HDMI Video 1080p 60 3D Audio PCM DTS DOLBY HD DE...

Page 24: ...RELAY1 OFF RELAY2 OFF 01 I O TYPE IR SRC None 02 I O TYPE IR SRC None 03 I O TYPE IR SRC None 04 I O TYPE IR SRC None 05 I O TYPE IR SRC None 06 I O TYPE IR SRC None 07 I O TYPE IR SRC None 08 I O TY...

Page 25: ...SRC None ARC OFF CAT5 SNY 2015 HPD ON Link ON HDCP ON DDC GOOD Control I O TYPE IR SRC External I O 04 PWR OFF 05 Input 05 Mode AUTO DVI HDMI VM UNMUTED Output ON HDMI NONE HPD OFF Link OFF HDCP NONE...

Page 26: ...BLE 03 IN HDMI V 90 B 20 L 12 M 12 T 12 LP 00 MUTE DISABLE 04 IN HDMI V 90 B 20 L 12 M 12 T 12 LP 00 MUTE DISABLE 05 IN HDMI V 90 B 20 L 12 M 12 T 12 LP 00 MUTE DISABLE 06 IN HDMI V 90 B 20 L 12 M 12...

Page 27: ...ro project 1 Choose your all in one matrix MC in the Setup Controllers step Add IP address which must match IP address configured to matrix 2 In the Controlling Flow step drag the MC from the Devices...

Page 28: ...T Rx are typically dragged to the ports labelled CAT5Output_1 8 4 Source and other in rack equipment are typically controlled on the Expansion I O Ports of the matrix MC If you need to adjust from IR...

Page 29: ...r NC inactive with 12A 250VAC resistive switching capacity TCP IP 1 Supports 10 100BaseT up to 100Mbps Video Bandwidth TMDS bandwidth 10 2 Gbps Link Single Link DDC Signal Data Input DDC Signal 5 Volt...

Page 30: ...his device near water 4 Clean only with dry cloth 5 Install in accordance with the manufacturer s instructions 6 Do not install near any heat sources such as radiators heat registers stoves or other a...

Page 31: ...ail tech keydigital com Repairs and Warranty Service Should your product require warranty service or repair please obtain a Key Digital Return Material Authorization RMA number by contacting us at Pho...

Page 32: ...ications where high end video and control are important Key Digital is at the forefront of the video industry for Home Theater Retailers Custom Installers System Integrators Broadcasters Manufacturers...

Reviews: