green crocodile clip to the neutral of the system
Carry out the initial checks Press the test button. A beep will
sound as the test is conducted and the value of PSC will be
displayed.
It is good practice to disconnect the phase lead first
Note:
PSC function has a power factor correction of 0.84.
Voltage(V)
PSC = x 0.84
LOOP(
Ω
)
If the PSC ranges are selected whilst connected to a socket
outlet via the mains lead KAMP11UK, a test will take place
between Phase and Earth due to the fixed wiring of the mould-
ed mains plug i.e.
a Phase-Earth fault current test.
When measuring the Phase-Earth fault current with the ATT
mode activated, RCD won't trip as well as at the LOOP test.