For this example the maximum value is 1667
Ω
, the loop tester
reads 12.74
Ω
and consequently the condition RA is <
_ 50/Ia is
met. It also important to test the operation of the RCD using a
dedicated RCD tester in accordance with the international
standard IEC60364 for a TN system. The following condition
shall be fulfilled for each circuit.
Zs <
_ Uo/Ia where Zs is the earth fault loop impedance voltage is
the nominal voltage between phase and earth and Ia is the
current that causes the automatic disconnection of the
protective device within the time stated in the following table.
Uo (Volts)
T (seconds)
120
0.8
230
0.4
400
0.2
>400
0.1
Fig 6