GENERAL DESCRIPTION (Fig.1.1) 

 
The Thermomatic RSM 20/FB is a wall mounted 
water jacketed vertical tube Combination Boiler fitted 
with a copper coil to give an immediate supply of hot 
water. 
The appliance is room sealed and fitted with a coaxial 
duct for fan powered ventilation, designed for exit to 
either side or to the rear of the appliance. 
The copper coil containing 2 litres of hot water is 
indirectly heated, giving an immediate and continuous 
hot water supply. 

The central heating pump will not operate until 
the boiler temperature reaches 60°C

. The pump is 

controlled by a capillary thermostat called the anti-
condensing thermostat. In addition, a bimetallic 
priority thermostat will stop the pump as soon as 
domestic hot water is drawn. This allows the full heat 
output to be directed to supplying hot water only. 
The appliance jacket extends to burner level, so the 
walls of the combustion chamber are water-cooled. 
This prevents the intense local heating usually 
associated with combination boilers and considerably 
prolongs the appliance life. 
The domestic hot water, being indirectly healed 
through a coil of a larger diameter than normally 
used, is not so easily affected by calcium impurities 
that build up lime scale. This together with the flexing 
of the coil due to temperature changes, means 
calcium "build-up" is considerably lessened. 

With the Summer/Winter switch set to Winter the 
appliance will automatically adjust to the central 
heating output, which may be a single radiator, ot 
any number within the heat ouput of the appliance. 
The Thermomalic does not require a 'by-pass' and all 
radiators can be fitted with thermostatic radiator 
valves. 
Unlike many other combination boilers, the Ther-
momalic will operate on low water pressures. The 
boiler within the casing is cylinder shaped and fitted 
with vertical copper flue tubes through which the gas 
products pass. These tubes are fitted wiih stainless 
steel baffles to increase efficiency and to rapidly 
conduct the heat from the gas products to the water 
contained within the cylindrical heat exchanger. 
An extended copper coil fitted around the vertical 
flue tubes is within the water content. The water 
content connects to the central healing system and 
indirectly heats the domestic water passing through 
the coil. 
A SIT Controls multifunctional control with electric 
ignition is used and temperatures of both central 
heating and hot water ate controlled by capillary 
thermostats. 
The flue extract fan incorporates a pressure control 
switch which activates the gas control. In the case of 
a fan failure of any kind the gas control fails to safely.  

It is recommended that a scale inhibitor should 
be fitted in hard water areas. 

 

FIG.1.1   INTERNAL DESIGN 

 

 

 

 
 
 
 
 

 
 
 
 
 

Manual air vent cock 

Gas control valve 

Stainless steel burners 

Ignition electrode 

Pocket for an anticondensing thermostat phial 

Pocket For safety thermostat phial 

Pocket for boiler healing thermostat phial 

Water temperature gauge 

Automatic air vent 

10 

Fan motor 

11 

Expansion vessel 

12 

Stainless steel Hue baffles 

13 

Boiler shell 

14 

Domestic hoi water copper coil 

15 

Circulating pump 

16 

Pressure relic! Safely valve 

17 

Water pressure gauge 

18 

Bimetallic priority thermostat 

19 

Air pressure microswitch 

20 

Air pressure switch body 

21 

Concentric flue/air pipe 

22 

Flue terminal 

23 

Flue hood 

24 

Electronic control box 

25 

Room sealed combustion chamber 

26 

Flame detection probe 

27 

Mini expansion vessel (Domestic) 

Summary of Contents for Thermomatic RSM20/FB

Page 1: ...UNDER FRONT PANEL ON BURNER COVER Manufactured by THERMOMATIC SRL Casalecchio Di Reno Bologna Italy exclusively for High Efficiency Domestic Commercial Boilers 34 West Common Road Hayes Bromley Kent...

Page 2: ...Page 2...

Page 3: ...91931199 Overheat thermostat Ranco LM7 P5 043 Anticondensing Thermostat Imit TR2 Electrical supply 240V 50HZ Power consumption 180 W Internal fuse rating 3A Weight empty 77 kg 169 7 Ib Weight full 92...

Page 4: ...Positioning 4 2 13 Replacing DHW Expansion Vessel 6 7 21 Flue Positioning 4 3 14 Flue Connection 4 4 14 Replacing Automatic Air Vent 6 8 21 Flue Connection 4 5 14 Replacing CM Expansion Vessel 6 9 21...

Page 5: ...ted with thermostatic radiator valves Unlike many other combination boilers the Ther momalic will operate on low water pressures The boiler within the casing is cylinder shaped and fitted with vertica...

Page 6: ...hoi water demand is satisfied the bimetallic priority thermostat allows the pump to restart When only a small domestic hot water flow is drawn the bimetallic priority thermostat does not intervene 2...

Page 7: ...he allowed value then an additional vessel must be provided connected as close as possible to the appliance heating return E Pressure relief safety valve The valve outlet must be routed to a suitable...

Page 8: ...ealed system is shown in Fig 3 3 3 3 2 Domestic hot water circuit See Fig 3 1 for connections An extended copper coil is filled which is healed from the primary water Starting from cold the appliance...

Page 9: ...ly An optional 2m extension flue system kit Pan No R3000014 is available which allows the maximum lengths to be increased lo 2840 and 2730 respective ly 3 4 4 If a vertical flue is required an optiona...

Page 10: ...icate with the same room or space or both must be on the same wall to outside air 3 5 APPLIANCE LOCATION 3 5 1 This appliance is not suitable for external installation 3 5 2 The wall on which the appl...

Page 11: ...EE Regulations and Local Regulations which apply The Thermornatic Combination Boiler is supplied for connection to a 240V 50Hz single phase The appliance is fused at 3A 3 6 2 The method of connection...

Page 12: ...Page 12...

Page 13: ...Flue hole 145 mm diameter f Insert the plastic plugs and screw in the fixing brackets to within 2 of 3 mm ol the wall face 4 3 Hang the T bar template on the fixing brackets and check that it is perfe...

Page 14: ...pipe cut from the plain end Any Flue Cut off exactly the same amount as removed from the air pipe Drill again a hole 3mm diameter at a distance of 16 mm from the end of pipe to the centre of hole e Cu...

Page 15: ...est point 2 3 1 off R3560632 Concentric roof terminal 118 length 120cm 4 1 off Roofing tile 5 b Preparations Drill a hole 130mm on the roof in axis to the fan socket If this is not possible consider t...

Page 16: ...the wall bracket in the correct position to support the flue assembly when in place See Fig 4 6 k Separate the flue pipe with the terminal from the 1 metre length of 1OO mm diameter air pipe I Fit th...

Page 17: ...Page 17...

Page 18: ...lling loop assembly to the filling cock A including the other fibre washer supplied B Ensure that the assemble filling loop does not interfere with the operation of the gas cock G Tighten all connecti...

Page 19: ...ion sequence and the green light will illuminate when the burner has lit If the burner fails to light the appliance will go to lockout red light illuminated In this case the cause is probably air in t...

Page 20: ...ig 3 JO B 6 2 4Side panels After having removed the front top and base panels remove the two screws securing the instrument panel to the respective side panel Remove the respective side panel fixing s...

Page 21: ...TIC HOT WATER EXPANSION VESSEL ITEM 46 6 7 1 Refer to Sections 6 1 6 2 1 6 2 2 6 2 4 left hand side panel 6 3 drain DHW circuit and 6 4 6 7 2 Unscrew the vessel 6 8 AUTOMATIC AIR VENT ITEM 47 6 8 1 Re...

Page 22: ...lip from the respective phial boss 6 14 4 Trace the capillary to the control body 6 14 5 Safety overheat thermostat item 65 i Unscrew the reset button cover II Disconnect two leads iii Unscrew locknut...

Page 23: ...Remove the burner sections 6 16 1 to 6 16 7 above 6 17 2 Unscrew the injectors 6 17 3 Refer to 6 16 8 when reassembling Ensure the larger injector is fitted in the center burner bar 6 18 FLAME SENSIN...

Page 24: ...reload button tripped Unscrew the black cap of safety Thermostat and push the button to restore the contact Faulty safety Thermostat ST Replace it Is the motor stuck Release the motor or replace it R...

Page 25: ...the electrode position comparing to the burner it must not touch the burner If necessary replace the electrode The fan motor starts and the red light on the instrument panel comes on Does the burner...

Page 26: ...t call for heat When the w ater temperature of the boiler exceeds 60 C does the circulation pump start check w ithout draw ing w ater See condition 6 Is the circulation pump stuck Set SWS on w inter S...

Page 27: ...ape from the various vents of the htg system Is the non return valve blocked I the domestic w ater regulatory ball valve closed No Yes No Fill the boiler and the system up to 1 bar of pressure Restore...

Page 28: ...thermostat probes are removed for servicing and w rongly fitted into the respective sheathings Restore 1 bar of pressure in the boiler and in the heating system at cold No Yes FWith the burner alight...

Page 29: ...ermostat HT set on max Set HT to position min Insufficient gas delivery No Replace HT Set the HT temperature at maximum Insulate the pipeline Set the proper pressure to the gas valve see gas valve drw...

Page 30: ...ONDITION 11 A complete cleaning is necessary Wrong fitting of the flue pipe or of the air intake pipe Gas products smell Are the fire tibes of the heat exchanger and the baffles dirty Wrong installati...

Page 31: ...the filling flexible pipe leaking Water Leakage from the boiler Does w ater escape from the air vent valve Faulty air vent valve replace it Yes Is the w ater gauge leaking Is some w asher in the hydra...

Page 32: ...3 7 Replace the baffles the inner top panel fan and the flue elbow Connect the leads polarity immaterial and the pressure tubes red to red 8 3 8 Clean any debris from the burner chamber and order 8 4...

Page 33: ...Page 33...

Page 34: ...densin g Thermostat 65 3120112 Overheat Safety Thermostat 61 3023115 Boiler Heating Regulatory Thermostat 69 303201 On Off Summer Winter Switch Key No Code Part Denomination 67 3130201 Temperature Pre...

Page 35: ...omatic Air Vent Valve 70 3520131 Operating Light Neon Bulb 71 3020157 Lamp Holder 49 3030315 C H Expansion Vessel 53 3544410 Gas Control Valve Key No Code Part Denomination 43 3424110 Bimetallic Prior...

Page 36: ...LL VALVE ALBIFIL 43 3424110 BIMETALLIC PRIORITY THERMOSTAT 46 3033315 INOX MINI VESSEL 47 3330343 AUTOMATIC AIR VENT 49 3030315 CH EXPANSION VESSEL 8 LITRES 53 3544410 GAS VALVE 59 3450113 ELECTRODE 6...

Page 37: ...Page 37 Complete boiler wiring schematic...

Page 38: ...Page 38 New Thermomatic wiring diagram as from S No 00054 When wiring the boiler in conjunction with a time switch remove the link plug from the 5 wire block left hand side at the bottom...

Page 39: ...Page 39 Examples of standard wiring connections to most popular models...

Page 40: ...Page 40...

Page 41: ...he boiler has been prepared Should it be necessary to do some adjustment for example if the supply pressure is another than the mentioned one see the specific label precede as follows 2 Connect a suit...

Page 42: ...mm of diameter through an outer wall in line with the flue bend 4 see also the dimensions in the Boiler Installation Instructions INSTALLATION l Properly position the centralising springs 9 insert the...

Page 43: ...r air pipe junction 7 1 mt Flue pipe extension 060 8 Imt Air pipe extension 0100 9 3566296 Centralising spring 10 3566293 Sealing washer fixing clamp for pipe junction 11 3566297 Finishing washer for...

Page 44: ...mp body Important Check that the pump be set at a velocity that suits the system EXPANSION TANK Remove the front panel and empty the boiler Unscrew the connection and remove the tank taking care to ca...

Page 45: ......

Page 46: ......

Reviews: