4

4

4.9 End of programming

The programming routine

is repeated once more.

The values set until now

can be checked and mod-

ified.

The programming routine

wil be left and all values

set will be stored as new

parameters.

Afterwards the device is

ready for operation.

4.8 SET value

The device will be set to

the set point by pressing

the red SET/RESET key

or activating the

SET/RESET input.

SET value -199999...

999999 (number of deci-

mal places depends on

the decimal point option)

Tachometer/Frequency meter

522K

(

524K

: Operating mode frequency meter)

1. Description

• 6 digit frequency meter

• Red LED display, character height 8 mm

• Display range from 0 to 999 999 

• Leading zeros suppression. 

• Programming via two setting keys on the front

side

• During programming, the display guides the

user with text prompts

• Value conversion and display in 1/s or 1/min

• Optional optocoupler output

2. Inputs

INP A

Dynamic count input. 

3. Optocoupler output 

(optional)

Active at f=0. Can be used e.g. to activate a „No

operation“ lamp.

4. Programming routine

The programmable parameters of the device are

described below, in the order in which they can

be set. The device is fully programmed after one

pass of the routine.

The first values stated correspond to the factory
settings

4.1 Polarity of the inputs

npn: switching for 0 V

pnp: switching for +UB

For programming the decimal point see 4.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for 521K

Page 1: ...astics paper glass textile and other processing indus tries Over voltages at the terminals of the digital dis play must be kept within the limits in Category II If the digital display is used to monit...

Page 2: ...r Continued in point 4 of 522K on page 4 Operating mode time meter Continued in point 4 of 523K on page 6 Pulse counter Position indicator 521K 524K Operating mode pulse counter 1 Description 6 digit...

Page 3: ...ach pulse edge of INP A and INP B will be counted 4 3 Input mode 4 4 Multiplying factor It can be set from 00 0001 up to 99 9999 The decimal point is set to 4 decimal places 0 is not accepted 4 7 SET...

Page 4: ...ter Red LED display character height 8 mm Display range from 0 to 999 999 Leading zeros suppression Programming via two setting keys on the front side During programming the display guides the user wi...

Page 5: ...to 4 decimal places 0 is not accepted 4 4 Dividing factor 4 6 Display mode Value conversion and display in 1 s Value conversion and display in 1 min 4 7 Max time to wait until 0 is displayed This par...

Page 6: ...while the count is active Programming via two setting keys on the front side During programming the display guides the user with text prompts Time meter operating modes Counting while INP B is inactiv...

Page 7: ...RESET input locked only electrical reset via the SET RESET input only manual reset via the red SET RESET key 4 8 End of programming The programming routine is repeated once more The values set until n...

Page 8: ...nsitivity Low 0 2 V DC High 4 30 V DC Pulse shape any Schmitt Trigger inputs Optocoupler output optional NPN optocoupler with open collector and open emitter max switching performance 30 V DC 10 mA at...

Page 9: ...9 9 8 Dimensions Panel cut out 22 2 0 3 x 45 0 6 mm Front bezel Counter sinking Af3 DIN 74 1...

Reviews: