background image

TBC  OPR 071019

3-1

 SECTION 3 - OPERATING INSTRUCTIONS

3.1

GENERAL

Interconnections between a stabilized Battery Charger Power Supply, and its load are as critical
as the interface between other types of electronic equipment. If optimum performance is
expected, certain rules for the interconnections must be observed by the user. These rules are
described in detail in the following paragraphs. 

3.2

DC (OUTPUT) GROUNDING

Connections between the Battery Charger Power Supply and the load Goad and sensing con-
nections) may, despite all precautions such as shielding, twisting of wire-pairs, etc., “pick-up”
radiated noise of a wide frequency spectrum. To minimize these undesired effects, one side of
the Battery Charger Power Supply output/load circuit must be grounded. 

Successful DC grounding depends on careful analysis of the individual situation and only gen-
eral guide lines can be provided here. One of the major points, however, is to avoid GROUND
LOOPS. Ground loops are created when two (or more) points are grounded along the output cir-
cuit. Due to the wire impedance between the grounded pOints, a noise voltage is developed
which is superimposed on the load. The only way to avoid ground loops is to investigate the out-
put circuit (including the connected load) with an ohmmeter, for any resistance to ground. A sin-
gle DC ground point can be selected only if the output circuit is completely isolated. A single
point is selected along the Power Supply output/load circuit and this point is returned to ground
with a single wire. The exact location of this “best” DC ground-point is entirely dependent on the
application at hand. For single, isolated loads, the DC ground-pOint may be located directly at
one of the output terminals of the Power Supply which may be connected to ground. If Error
Sensing is employed, DC ground can be established at the remote load. In case of an internally
grounded load, the DC ground is automatically established directly at the load. 

3.3

LOAD WIRE SELECTION

A realistic model for a voltage stabilized Battery Charger Power Supply must, for example,
include a series resistance, representing a small DC and low frequency source impedance; in
series with an inductance, representing the source impedance at higher frequencies. This is
because of the variation in the equivalent characteristic output circuit impedance as the fre-
quency changes. Load wire selection should be made with those facts in mind. The load wire
size should not only be selected for minimum voltage drop (Error Sensing, as discussed below,
will take care of that), but also the series inductance of the load wire must be kept as small as
possible compared to the source inductance of the Battery Charger Power Supply (Error Sens-
ing cannot compensate for this). 

3.4

LOAD CONNECTION, METHOD 1 (LOCAL ERROR SENSING)

The most basic Battery Charger Power Supply interconnection for maintaining Batteries con-
nected across a load consists of 2-wire connection from the rear output terminals. The load
leads should be tightly twisted to reduce “pick-up” from stray magnetic fields. 

Figure 3-1 shows the correct and incorrect methods of connecting single and multiple loads with
local sensing. Remote Sensing should be used for the most critical load (see PAR. 3.5). Local
error sensing links must be connected with the proper poS to +M and –S to –M. The TBC
Battery Charger Power Supplies are shipped with links (jumpers) that connect the Sensing ter-
minals directly to the Monitor terminals. These links should be removed when remote sensing is
employed. 

Summary of Contents for TBC 12-50M

Page 1: ...fice in New York 718 461 7000 requesting the correct revision for your par ticular model and serial number 3 The contents of this manual are protected by copyright Reproduction of any part can be made...

Page 2: ......

Page 3: ...eration 3 3 1 1 TBC Series Rack Mount Battery Charger Power Supply ii 1 2 TBC Mechanical Outline Drawing 1 5 2 1 TBC Series Except TBC 24 120M and TBC 48 60M Front Panel Controls and Indicators 2 2 2...

Page 4: ...ii TBC OPR 071019 FIGURE 1 1 TBC SERIES RACK MOUNT BATTERY CHARGER POWER SUPPLY...

Page 5: ...senses that the battery is not absorbing current from the Charger but rather is supplying current back to the TBC This sensor is very sensitive It can respond to a reverse current of less than 50 mil...

Page 6: ...00 240V a c 12 VOLT MODELS TBC 12 20M 12 11 15 22 9 3 7 90 A 1 21 9 5 TBC 12 50M 12 11 15 53 9 3 7 90 A 1 25 11 4 TBC 12 100M 12 11 15 100 18 9 90 A 1 TBC 12 120M 3 12 11 5 15 120 22 11 81 A 1 33 15 2...

Page 7: ...c max Startup Time 900mS max Holdup Time 30mS max EMI FCC Class A Power Factor 0 99 typ 100V a c input rated output Output Characteristics Source Effect typical 0 8 115 15V a c 230 30 V a c Minimum M...

Page 8: ...sensing and logic outputs for status mon itoring The DC output has factory preset voltage and current limit adjustments The TBC has an overvoltage protection circuit that senses the output at the Mon...

Page 9: ...071019 5 FIGURE 1 2 TBC MECHANICAL OUTLINE DRAWING 1 5 1 6 Blank 4 5...

Page 10: ......

Page 11: ...y 3 1 2 digit LCD meter for reading current 4 EQUALIZE TIME timer 0 1 to 99 9 hour timer that can be set to establish the duration of the Equalize cycle 5 START switch Pressing START button starts the...

Page 12: ...BC 24 120M AND TBC 48 60M FRONT PANEL CONTROLS AND INDICATORS b Rear Panel The TBC has two output power terminals for connecting to the battery and or load It also has two terminal blocks TB1 and TB2...

Page 13: ...the TBC A short circuit or logic low between these two terminals will return the TBC to operation Logic high is between 2 4V and 24V d c logic low is between 0V and 0 4V d c When high this terminal ca...

Page 14: ...ay be hazardous Refer to Table 1 2 for input current specifi cations and ensure source power is off and TBC Power ON OFF is set to OFF before proceeding a Remove the four screws from the small panel l...

Page 15: ...is imperative that the chassis of the power supply be returned to AC ground with a separate lead A grounding terminal is pro vided on Terminal Block TB3 for this purpose a Terminal Block TB3 on the C...

Page 16: ...ed with the TBC Four screws flat head 10 32 x 1 2 100 degrees coun tersink six screws truss head phillips 10 32 x 3 8 black and six Internal lockwashers no 10 are also included The mounting flanges ea...

Page 17: ...TBC OPR 071019 2 7 2 8 Blank FIGURE 2 6 RACK MOUNTING...

Page 18: ......

Page 19: ...nt may be located directly at one of the output terminals of the Power Supply which may be connected to ground If Error Sensing is employed DC ground can be established at the remote load In case of a...

Page 20: ...oad wire voltage drops Observe polarities The negative Sensing wire must go to the nega tive load wire and the positive Sensing wire goes to the positive load wire The Remote Sensing terminals must be...

Page 21: ...her terminal 9 on TB1 for all the TBC units in operation see Figure 2 3 NOTE To operate up to three TBC Battery Charger Power Supply units in parallel set the desired output voltages at the load for e...

Page 22: ...3 4 TBC OPR 071019 FIGURE 3 3 SUGGESTED WIRING FOR UP TO THREE TBC UNITS WITH REMOTE SENSING AND REMOTE CONTROL...

Reviews: