EMI CONDUCTED:  

FCC Class A

SAFETY: 

 All units designed to meet UL 1950D3, UL 478, CSA Electrical Bulletin 1402C, VDE 0806, TÜV Rheinland

EN60950   and IEC 950  Safety Standards. RAX are CE marked per the Low Voltage Directive (LVD), EN60950.  [The stan-

dards do not apply with DC input operation].

REMOTE ERROR SENSING:  

RAX 3.3-35K and 5-35K models, up to 0.25V per load wire. All other models, up to 0.4V per

load wire. The power supply is factory set with links in place.

REMOTE CONTROL ON/OFF:  

“High,” 2.4V-24V (or open), unit ON

“Low,” 0.0V-0.4V (or closed), unit OFF

When Remote Control (RC) is at “Low” level, the output voltage remains Vo <0.5V.

Vo <5% of nominal voltage for 12, 15, 24, 28, and 48 volt models.

III — OPERATION       UNIT WILL NOT WORK WITH SENSE LEADS DISCONNECTED (SEE FIG. 2).

INSTALLING THE POWER SUPPLY:  

Refer to Figure 4. The unit may be mounted on one of the three mounting surfaces.

Mounting holes are provided for each mounting style. The air surrounding the power supply must not exceed the ambient val-

ues given in the graph in Figure 1.

CONNECTING AND SWITCHING THE LOAD:  

The load is connected as shown in Figure 2. Error sensing may be done at

the load terminals to compensate for voltage loss in the connecting wires. The jumper links must therefore be removed from

the sense terminals.

SELECTING INPUT VOLTAGE:  

Input voltage is selected with a jumper. Refer to Figure 3. The power supply is delivered

for 120V a-c operation. Change the jumper to the position marked “230V” to operate the unit from a nominal 220-240V a-

c or 320V d-c source.

VOLTAGE ADJUSTMENT:  

The unit is provided with a voltage adjustment control. To adjust voltage, first place the unit under

an operating load, then monitor the + and - sense terminals with a precision voltmeter and turn the voltage control to the

desired operating value. Refer to Table 1 for Adjustment Range.

CHANGING FUSE:  

Remove the cover to replace a fuse. (Refer to Figure 3.) The fuse holder will accept two sizes, either:

KEPCO P/N: 541-0084 or Manufacturer SOC P/N ST4-6.3A-N1 (1/4” x 1-1/4”)

KEPCO P/N: 541-0099 or Manufacturer Littelfuse P/N Type F (5mm x 20mm)

REMOTE TURN-ON TURN-OFF 

When power is on at the source the unit may be turned on or off with the remote control fea-

ture. The output of the remote turn-on/off RC (remote control) terminals operates at TTL logic levels (2.4V-24V “high” and 0.0

to 0.4V “low”). The unit is turned off by bringing the RC terminals to “low” logic level with a switch or solid state device. If the

remote on/off feature is not desired, the terminals should be left open.

FIGURE 1.  TEMPERATURE DERATING                               FIGURE 2.  CONNECTING THE LOAD WITH ERROR SENSING

LINKS

(SEE NOTE)

NOTE:

THE SENSE LEADS MUST NEVER BE DISCONNECTED FROM THE OUTPUT.  IF THE

SENSE LEADS ARE ALLOWED  TO FLOAT FREE OF THE OUTPUT, THE OUTPUT VOLT-

AGE WILL RISE TO THE OVERVOLTAGE POINT  AND THE UNIT WILL SHUT DOWN.

FOR REMOTE SENSING CONNECT THE SENSE TERMINALS TO THE LOAD AS

SHOWN, AND REMOVE  THE  TWO SENSING  LINKS.

FOR LOCAL SENSING LEAVE THE SENSING LINKS IN PLACE AND CONNECT

THE LOAD DIRECTLY TO THE BUS BAR.