If the brake is used in connection with other electronic accessories, the user is responsible to ensure
compliance with EMC requirements. Compliance with applicable standards concerning the design and
operation of components, sub-assemblies or equipment employed shall not relieve the user and manufacturer
of the overall system from their obligation to furnish proof of conformity of the overall system with such
standards.
Rectifier type
Rated input voltage range
U
1
/VAC (40-60 Hz)
DC at L-load
(ADC)
Capacitor
(nF(VAC))
Bridge rectifier
32 07.23B.0
up to 400 (+10%)
up to 2.0
no additional
interference suppression
measures required
Half-wave rectifier
32 07.22B.0
up to 500 (+10%)
up to 2.0
no additional
interference suppression
measures required
Overexcitation rectifier
32 17350E..
48-120 (
±
10%)
220-415 (
±
10%)
480-525 (
±
10%)
up to 3
no additional
interference suppression
measures required
Overexcitation rectifier
32 17.2.B..
110-230
220-415
up to 1.5
up to 1.0
no additional
interference suppression
measures required
Table 17/1
Rectifier input voltage (max.)
(VAC)
Recommended disconnection voltage for DC side switching
(V)
250
700
440
1200
550
1500
Table 17/2