TROUBLESHOOTING 
 

Problem 

Solution 

No output change with level change 

Check wiring; verify that the correct input 
voltage is applied 
Verify that liquid is filling the sensor gap 
Check for dense foam or dried product in 
the gap.  Switch may not function properly 
if either condition exists. 
Check sensor phono plugs for a good 
connection.  Unplug and Re-plug each 
connection. 
Check for excessive aeration in process 
fluid.  This is particularly important in 
viscous fluids. 

The output is “chattering” 

Check wiring; verify that the correct input 
voltage is applied 
Check for turbulence.  Relocate switch or 
isolate from turbulence 
Check for excessive aeration in process 
fluid.  This is particularly important in 
viscous fluids. 

 