Wiring 

It is recommended that conduit be installed onto the ¾” NPT connection on the electronics housing.  A seal drain fitting 
should be used to prevent moisture from entering the switch.  All wiring, conduit, and electrical fittings must conform to 
local electrical codes for the location selected.  If the switch is to be used in a Hazardous Area, the applicable codes of the 
National Electrical Code must be followed as well. 
 
 

Relay Version

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

1.  Connect power wiring 

a.  AC – Hot (L2), Neutral (L2), and Ground (G) 
b.  DC – Positive (L1), Negative (G) 

2.  Connect relay wiring (see diagram) 
3.  Connect Manual Self-Test terminals to a remote pushbutton (maximum distance 30 feet). 
4.  Adjust failsafe jumper 

a.  HLFS – top (2) pins 
b.  LLFS – bottom (2) pins 

 
 
The following table shows the relay condition for each switch state: 
 

Media 

Level 

Fail Safe 

Setting 

Relay 

Condition 

Relay Terminals 

NC to C 

NO to C 

Above 

Setpoint 

HLFS 

De-Energized 

Closed 

Open 

LLFS 

Energized 

Open 

Closed 

Below 

Setpoint 

HLFS 

Energized 

Open 

Closed 

LLFS 

De-Energized 

Closed 

Open 

 
 
 

  

 
 
 
 
 
 
 
 
 