background image

3

Installation Instructions Kemlan Natural Draft Electronic Ignition Gas Fireplaces

Before Installation

The Natural Draft Electronic Ignition (N.D.E.I.) flue
system shall be installed by authorized personnel in
accordance with the manufacturer’s installation
instructions, local gas fitting regulations, municipal
building codes, electrical wiring regulations, and any
other statutory regulations. Contact your local building
authorities about restrictions and installation inspections
that may be required. If in doubt contact your local
dealer or Kemlan’s Head office.

IMPORTANT AUSTRALIAN CODES:

Australian Standards AS 5601 Gas Installation

Australian Standards AS 3000 Electrical 

Important Safety Notes

Comply with all instructions in manual including 
clearances to combustible material.

Do not operate without fully assembling all 
components.

All open gas fires require ventilation in the room. 

Do not connect to any other air distribution duct or 
system.

An A.G.A approved cowl is required at flue terminal.

Air movement of systems- A decorative gas log fire 
must not be installed where the operation of any 
ventilation system, fan or air blower could in any 
circumstances cause the air pressure to be less than 
atmospheric at the appliance.

Do not block or restrict chimney.

After installing appliance check that the flue draws
well with smoke pellet.

Kemlan recommends that all gas fires be serviced 
every year.

All gas units must be fitted by a licensed gas fitter.

It is the responsibility of the gas fitter to follow the 
regulations set out in the Gas Code that dictate the 
procedures to follow when installing a gas appliance, 
particularly regarding gas pipe sizing and checking of 
pressures.

Installation

1

The N.D.E.I. system is supplied with all 
required electrical fittings. Work needs to be 
undertaken by a licensed electrician if extending 
wiring. Wiring requires clearance of minimum 
100mm to flues and fireplace body due to heat. See 
Wiring diagram page 15. Wiring must be positively
secured away from heat source.

2

An isolation switch needs to be provided if 
connecting within fireplace framework.

3

Build frame to specifications provided. Note: 80mm
clearance above fireplace and 5mm to front surface
of firebox.

4

Unit located on 10mm fiber cement sheeting. 
Sheeting requires 5 x 50mm holes drilled for air 
access to gas burner.

5

Unit and flues to be installed prior to plastering.

6

Gas line run to desired position prior to plastering.

7

A minimum height of 150mm from floor needs to be 
available for use of front fascia on firebox.

8

Clearance of 50mm to vertical flue.

9

Allow for a minimum flue height of 3.6m.

10 All flue components to be riveted together.

11 Ventilation is required under fireplace to allow for 

sufficient air to gas burner. (Note Elevation drawing)

12 Rooms with Gas Open Fires require fresh air vents 

of 400sq centimetres for each Decorative Gas, Coal 
Fire.

Summary of Contents for Horizon Natural Draft Electronic Ignition

Page 1: ...Installation Instructions Horizon Natural Draft Electronic Ignition Gas Fireplaces...

Page 2: ...Ignition Gas Fireplace DATA PLATE Refer to data plate for information in respect to gas pressure consumption and gas type Natural or LPG Data Plate is located under the gas burner and is accessed by...

Page 3: ...pellet Kemlan recommends that all gas fires be serviced every year All gas units must be fitted by a licensed gas fitter It is the responsibility of the gas fitter to follow the regulations set out i...

Page 4: ...CONNECTION UNDER BURNER Installation Instructions Kemlan Natural Draft Electronic Ignition Gas Fireplaces Measurement and Specifications of N D E I SINGLE SIDED CANTILEVER DOUBLE SIDED UNDER BURNER U...

Page 5: ...5 Installation Instructions Kemlan Natural Draft Electronic Ignition Gas Fireplaces Framing Dimensions DOUBLE SIDED SINGLE SIDED B INCLUDE 10MM PLASTERBOARD...

Page 6: ...6 Installation Instructions Kemlan Natural Draft Electronic Ignition Gas Fireplaces Section SINGLE SIDED ELEVATION CANTILEVER ELEVATION SINGLE SIDED SECTION CANTILEVER SECTION Elevation...

Page 7: ...pilot and main burner will then ignite from pilot Burner is turned off by turning off wall switch System does not have a high low burner switch Laying the fire Coal Pebble Evenly spread a bag of Vermi...

Page 8: ...ireplaces Laying the fire Coal Pebble MARK 2 COALS 440 500 390 X 240 MARK 2 COALS 600 460 X 260 MARK 2 COALS 700 580 X 260 MARK 2 PEBBLES 700 580 X 260 MARK 2 COALS 700 800 600 X 155 MARK 2 PEBBLES 70...

Page 9: ...s two holes on the underside to position in place 3 LOCATE LOG NO S 2 3 Two front log NO S 2 3 are supplied to fit into the space between the metal frame and the ceramic base These logs do not cover t...

Page 10: ...log is placed on the rear log in the centre of the burner Charred effect facing toward the left of the burner The front rests on logs 2 3 on the join LOCATE LOG NO 10 This log is located on the rear l...

Page 11: ...og no s 2 and 3 are supplied to fit into the space between the metal frame and the ceramic base These logs do not cover the front burner ports but are designed to deflect the front flame back into the...

Page 12: ...large rear log no 1 6 LOCATE LOG NO 7 The charred effect of the log is positioned on the smaller coal in the centre of the burner on the right hand side The right hand side of the log is positioned be...

Page 13: ...e ignition system Working correctly there will be no spillage Unit should cut out if not enough draw to ensure proper functioning 2 Initially the Kemlan coal fire may burn with a slightly blue flame A...

Page 14: ...14 Wiring Diagram For further service information contact Kemlan Australia Head Office 59 Pineapple St Zillmere QLD 4034 Telephone 07 3263 8488 Facsimile 07 3263 6452 www kemlan com...

Reviews: