Kelvinator KSV80HRD Installation Manual Download Page 8

8

Installation instructions

1  Flaring work

Main cause for refrigerant leakage is due to defects in the flaring 
work. Carry out correct flaring work using the following procedure:

Oblique

90 C

Roughness

Burr

A:  Cut the pipes and the cable.

1.   Use the piping kit accessory (if applicable) or pipes purchased locally.

2.   Measure the distance between the indoor and the outdoor unit.

3.  Cut the pipes a little longer than the measured distance.

4.  Cut the cable 1.5m longer than the pipe length.

B:  Burr removal

 

1. 

 Completely remove all burrs from the cut cross section 
of pipe/tube.

 

2. 

 Face the end of the copper pipe/tube in a downward 
direction as you remove burrs in order to avoid burrs 
dropping into the tubing.

Pipe

Reamer

Face down

WARNING

caution

C:  Putting flare nut on

Remove flare nuts attached to indoor and outdoor unit, 
then put them on pipe/tube having completed burr removal

Note: It is not possible to put them on after flaring work.

Flare nut

Copper tube

D:  Flaring work

• 

Carry out flaring work using flaring tool as shown below.

• 

 Firmly hold copper pipe in a die according to the dimension 
shown in the table below.

Refrigerant pipe connection

Outer diam. (mm)

A(mm)

Max.

Min.

φ

6.35

1.3

0.7

φ

9.53

1.6

1.0

φ

12.7

1.8

1.0

φ

16.0

2.4

2.2

 

Bar

Copper pipe

Clamp handle

Red arrow mark

Cone

Yoke

Handle

Bar

"A

"

 

Flaring tool assembly torque

Outer diam.

Tightening torque 
(N.m)

Additional Tightening 
Torque (N.m)

φ6.35

1.6

2.0

φ9.53

3.0

3.5

φ12.7

5.0

5.5

φ16.0

7.5

8.0

WARNING

caution

• 

 Excessive torque can break nut depending on installation 

conditions.

E: Check

• 

Compare the flared work with the adjacent diagram.

• 

 If flare is found to be defective, cut off the flared section and 
do flaring work again.

Smooth all round

 Improper flaring

Even length

all round

Summary of Contents for KSV80HRD

Page 1: ...Inverter Split Room Air Conditioner Installation Manual KSV25HRD KSV35HRD KSV52HRD KSV70HRD KSV80HRD Refrigerant R410A...

Page 2: ...our local Electrolux Customer Care Centre ENVIRONMENTAL TIPS environment Information on disposal for users Most of the packing materials are recyclable Please dispose of those materials through your l...

Page 3: ...esponsible for their safety 7 Children should be supervised to ensure that they do not play with the appliance WARNING warning Before obtaining access to terminals all supply circuits must be disconne...

Page 4: ...nt welders or medical equipment salt laden air prevails such as close to coastal areas the air is contaminated with industrial vapours and oils the air contains sulphurous gas such as in hot spring zo...

Page 5: ...adhered to the air conditioner will not perform to specification may not be able to be serviced and the warranty may be voided The installation must allow for reasonable access by a service technician...

Page 6: ...he outlet in the water Installation of indoor unit Installation of Mounting Plate 1 The mounting plate should be installed horizontally As the water tray s outlet for the indoor unit is two way type d...

Page 7: ...of indoor unit cut off the tailings from the chassis when necessary As shown in Fig 1 a Cut off the tailings 1 when routing the wiring only b Cut off the tailings 1 and tailings 2 when routing both th...

Page 8: ...Remove flare nuts attached to indoor and outdoor unit then put them on pipe tube having completed burr removal Note It is not possible to put them on after flaring work Flare nut Copper tube D Flarin...

Page 9: ...age Test 1 Connect charging hose of manifold valve to charge end of low pressure valve both high low pressure valves must be tightly shut 2 Connect joint of charging hose to vacuum pump 3 Fully open t...

Page 10: ...accurate Operation Test 1 Before Operation Test a Do not switch on power before installation is finished completely b Electric wiring must be connected correctly and securely c Cut off valves of the...

Page 11: ...own in the fig For 5 2kW is as below Clasp of RJ45 plug of network cable shall aim at the notch of RJ45 terminal to be installed The clasp shall be towards inside as shown in the fig For 7 0kW and 8 0...

Page 12: ...12 Notes Notes...

Page 13: ...13 Notes Notes...

Page 14: ...14 Notes Notes...

Page 15: ...t claimed is due to faulty or defective parts or workmanship Electrolux is not liable in the following situations which are not exhaustive a the Appliance is damaged by i accident ii misuse or abuse i...

Page 16: ...ator com au NEW ZEALAND phone 0800 436 245 fax 0800 225 088 email customercare electrolux co nz web kelvinator co nz For more information on all Kelvinator appliances or for dimension and installation...

Reviews: