Kelvinator KSV80HRD Installation Manual Download Page 6

6

Installation instructions

2.   Insert the piping-hole sleeve into the hole to prevent the 

connection piping and wiring from being damaged when 
passing through the hole.

Ø

Ø

55/ 65

Indoor

Outdoor

Wall pipe 

Seal pad

Installation of Drain Hose

1.   Connect the drain hose to the outlet pipe of the 

indoor unit. Bind the joint with binding tape.

drain hose

outlet pipe of 
indoor unit

outlet pipe of 

indoor unit

binding tape

2.  Put the drain hose into insulating tube.

insulating tube

drain hose

outlet pipe of 
indoor unit

binding tape

3.   Wrap the insulating tube with wide binding tape to prevent the 

shift of insulating tube. Slant the drain hose downward slightly 
for smooth drainage of condensing water.

outlet pipe of 
indoor unit

insulating tube

connected

binding tape

NOTE: The insulating tube should be connected reliably with the 
sleeve outside the outlet pipe. The drain hose should be slanted 
downward slightly, without distortion, bulge or fluctuation. Do not 
put the outlet in the water.

Installation of indoor unit

Installation of Mounting Plate

1.   The mounting plate should be installed horizontally. 

As the water tray's outlet for the indoor unit is two-way type, 
during installation, the indoor unit should slightly slant to water 
tray's outlet for smooth drainage of condenser water.

2.   Fix the mounting plate on the wall with screws.

3.   Be sure that the mounting plate has been fixed firmly enough 

to withstand about 60kg. Meanwhile, the weight should be 
evenly shared by every screw.

2.5kW and 3.5kW UNITS:

Ø55

Ø55

34.5

316

160

35

80

Above 150mm

from the ceiling

159

1048

346

70

70

70

39

83

90

55

130

81

90

55

94

166

281

575

158

685

205

70

5.2kW UNIT: 

Ø55

Ø55

34.5

316

160

35

80

Above 150mm

from the ceiling

159

1048

346

70

70

70

39

83

90

55

130

81

90

55

94

166

281

575

158

685

205

70

7.0 kW and 8.0 kW UNITS:

Ø55

Ø55

34.5

316

160

35

80

Above 150mm

from the ceiling

159

1048

346

70

70

70

39

83

90

55

130

81

90

55

94

166

281

575

158

685

205

70

Drill Piping Hole

1.   Slant the piping hole on the wall slightly downward to the 

outdoor side.

Piping hole

Units

( 55)

2.5 kW, 3.5 kW

( 70)

5.2kW, 7.0 kW and 8.0 kW

bulge

distortion

Flooded

Summary of Contents for KSV80HRD

Page 1: ...Inverter Split Room Air Conditioner Installation Manual KSV25HRD KSV35HRD KSV52HRD KSV70HRD KSV80HRD Refrigerant R410A...

Page 2: ...our local Electrolux Customer Care Centre ENVIRONMENTAL TIPS environment Information on disposal for users Most of the packing materials are recyclable Please dispose of those materials through your l...

Page 3: ...esponsible for their safety 7 Children should be supervised to ensure that they do not play with the appliance WARNING warning Before obtaining access to terminals all supply circuits must be disconne...

Page 4: ...nt welders or medical equipment salt laden air prevails such as close to coastal areas the air is contaminated with industrial vapours and oils the air contains sulphurous gas such as in hot spring zo...

Page 5: ...adhered to the air conditioner will not perform to specification may not be able to be serviced and the warranty may be voided The installation must allow for reasonable access by a service technician...

Page 6: ...he outlet in the water Installation of indoor unit Installation of Mounting Plate 1 The mounting plate should be installed horizontally As the water tray s outlet for the indoor unit is two way type d...

Page 7: ...of indoor unit cut off the tailings from the chassis when necessary As shown in Fig 1 a Cut off the tailings 1 when routing the wiring only b Cut off the tailings 1 and tailings 2 when routing both th...

Page 8: ...Remove flare nuts attached to indoor and outdoor unit then put them on pipe tube having completed burr removal Note It is not possible to put them on after flaring work Flare nut Copper tube D Flarin...

Page 9: ...age Test 1 Connect charging hose of manifold valve to charge end of low pressure valve both high low pressure valves must be tightly shut 2 Connect joint of charging hose to vacuum pump 3 Fully open t...

Page 10: ...accurate Operation Test 1 Before Operation Test a Do not switch on power before installation is finished completely b Electric wiring must be connected correctly and securely c Cut off valves of the...

Page 11: ...own in the fig For 5 2kW is as below Clasp of RJ45 plug of network cable shall aim at the notch of RJ45 terminal to be installed The clasp shall be towards inside as shown in the fig For 7 0kW and 8 0...

Page 12: ...12 Notes Notes...

Page 13: ...13 Notes Notes...

Page 14: ...14 Notes Notes...

Page 15: ...t claimed is due to faulty or defective parts or workmanship Electrolux is not liable in the following situations which are not exhaustive a the Appliance is damaged by i accident ii misuse or abuse i...

Page 16: ...ator com au NEW ZEALAND phone 0800 436 245 fax 0800 225 088 email customercare electrolux co nz web kelvinator co nz For more information on all Kelvinator appliances or for dimension and installation...

Reviews: