Kelvinator heat pump hot water system

5.  Release the pressure inside the tank by lifting up the lever 

on the pressure and temperature relief valve. Caution 
should be taken so the lever does not snap back as it 
could damage the valve seat. Once the lever is activated 
water will be discharged from the relief valve drainage 
pipe, relieving the pressure inside the storage tank. 

outlet

relief valve
activation 

lever

drainage 

pipe

6.  When water has stopped discharging from the relief valve 

drainage pipe, this indicates that the pressure inside the 
tank has now been reduced to atmospheric pressure. 
De-activate the lever on the relief valve, returning it to its 
normal position. 

7.  Drain the storage tank by undoing the connection to the 

tank inlet and placing your drainage solution in position 
as needed. Activate the relief valve lever, releasing the 
vacuum and allowing air to flow into the tank as the water 
drains out. Whilst the storage tank is draining, continually 
monitor the process and most importantly where the 
water is draining to. If at any time the draining needs to 
be halted, simply de-activate the relief valve lever. 

8.  Once the storage tank has been fully drained, flush the 

system by inserting a garden hose into the inlet of the 
storage tank. Allow water to enter the inlet and drain 
several times to ensure that all sediment is removed.

9.  De-activate the relief valve, returning it to its normal 

position. 

10. Reconnect the inlet piping to the storage tank and then 

turn on the isolation valve, located on the inlet piping to 
allow mains water to refill the tank. 

11.  Turn on the nearest hot water tap to allow air to be 

expelled from the system. Once water has begun to flow 
freely from the tap for a period of time and all air has 
been expelled from the system, close the hot water tap. 

 

 

 

 

 

 

 

 

 

 

 

Maintaining your hot water system

Regularly inspect the air inlet and outlet of the heat pump. 
Remove any foreign objects or blockages to allow the air to 
flow freely.
Once the hot water system is in use, sediment can 
accumulate in the system. 
In order to maximise the life of the hot water system, it is 
recommended that you flush the system every 5 years (more 
frequently in poor water quality areas) according to the 
below instructions: 

Drainage or flushing of tank

To flush or drain the storage tank:
1.  The power to the hot water system must be turned off at 

the switchboard.  Locate and turn off the circuit breaker 
that supplies the hot water system. 

2.  The water inside the tank may be very hot. Turn on the 

nearest hot water tap and allow it to run until the water 
coming out has reached a safe temperature for draining. 

 

 

 

 

 

 

 

 

 

 

 

 

3.   Before draining the hot water system assess the best area 

for the water to be directed (i.e. an outside drain) where  
it will not damage property or cause an unsafe situation  
to arise. 

4.  Turn off the mains water supply to the hot water system 

using the isolation valve located on the inlet piping. 

Maintenance

Summary of Contents for KCT27036A

Page 1: ...Heat Pump Hot Water System User Manual ...

Page 2: ...er system but contact your local Electrolux Customer Care Centre Meanings of symbols used in this manual are shown below warning This symbol indicates information concerning your personal safety caution This symbol indicates information on how to avoid damaging the hot water system environmental tips This symbol indicates tips and information about economical and ecological use of the hot water sy...

Page 3: ...off peak 1 where there may be approximately 8 hours of power available per day Connecting to night rate power supply may cause the automatic sanitisation function to not always comply with Australian Standard AS 3498 for legionella control warning This hot water system delivers water in excess of 50 C Water temperatures above 50 C can cause severe burns scalding or death Feel the water temperature...

Page 4: ...he heat pump and the warranty may be void if the heat pump is damaged as a result of freezing when there was no power available Ensure the following safety instructions are read and understood before using this hot water system warning Do not use this hot water system if it has at any stage been immersed in water Immediately call a licensed plumber gas fitter or authorised technician to inspect an...

Page 5: ...L KCT34036A 340L KCT34036B 425L KCT42536B Your heat pump hot water system components please tick Heat Pump KSE362HPCA Continuous power supply Extended off peak off peak 2 power supply System model number Heat pump serial number Storage tank serial number Installation date Installed by Notes System model number required to claim your STCs Heat pump model no Tank model no Power supply System model n...

Page 6: ... by taking heat energy from the surrounding air and then transferring the heat energy into water circulating from the hot water storage tank Since this energy is not created but simply moved and concentrated from one location to another it is a very efficient and cost effective when compared to a common electric hot water service Hot Water Storage Tank The hot water storage tank is where the hot w...

Page 7: ...ned of water to prevent damage due to freezing Follow the instructions on page 8 of this manual to safely drain and then re fill the hot water system as required Water quality Water quality can vary in different locations and affect the performance and safe operation of the hot water system If the water quality is not within the acceptable limits as indicated on this page the hot water system shou...

Page 8: ... activate the relief valve returning it to its normal position 10 Reconnect the inlet piping to the storage tank and then turn on the isolation valve located on the inlet piping to allow mains water to refill the tank 11 Turn on the nearest hot water tap to allow air to be expelled from the system Once water has begun to flow freely from the tap for a period of time and all air has been expelled f...

Page 9: ...er outlet connection is pointing away from any electrical components Bleed air from the water lines by twisting the knob on the valve anti clockwise Once water has begun flowing freely from the drainage tube for 10 seconds or more twist the knob clockwise to stop the valve from draining inlet outlet air bleed valve 13 Clean all filters in the hot water system including the tempering valve filters ...

Page 10: ...connected to this hole as part of the installation If an excessive amount of water is coming from this hole drainage pipe or anywhere else on the heat pump please call a service technician The sound of water flow inside the heat pump This is caused by the refrigerant and water flowing inside the heat pump It may be louder during the first few minutes of operation and is normal Short hissing sound ...

Page 11: ...d is due to faulty or defective parts or workmanship Electrolux is not liable in the following situations which are not exhaustive a the Appliance is damaged by i accident ii misuse or abuse including failure to properly maintain or service iii normal wear and tear iv power surges electrical storm damage excessive water pressure excessive inlet water temperature or incorrect power supply v incompl...

Page 12: ...ation about Kelvinator appliances please visit your retailer phone or email our Customer Care team or visit our website telephone 136 226 fax 1800 350 067 email hotwatersystems electrolux com au web www kelvinator com au Kelvinator We are part of the Electrolux family Share more of our thinking at www electrolux com au ...

Reviews: