44
Operating instructions CellaTemp PX 4x 5x 6x
8
Confirm parameter value
►
Press [MODE]�
> The display indicates the parameter�
The new value has been saved and
will take effect�
Ao.Fn
8
Ao.Fn
MODE
Exit operating parameter layer
►
Wait 30 seconds
or
► Press [˄ or ˅] to change to the parameter
End
� Then press [MODE] to
change to the functional menu�
► In the functional menu press [˄ or ˅] to change to the parameter
End
,
then press [MODE]�
If you press both keys [˄ ˅] only briefly, you will exit the layer (ESC) func
-
tion�
15 Error indications
Overload switching output
Sc
and flashing of the LED Out 1/2
Overtemperature
Display ot and the process value
change with 0�5 Hz
Incorrect connection of supply voltage The display is turned off
Supply voltage ≤ 16 V
The display is turned off
Temperature below mesuring range
The display shows UL
Temperature above measuring range
The display shows OL