45
Operating instructions CellaTemp PKx 6x
EN
20 General technical data
Load
max. 500 Ω
Switching output OUT1 / 2
Open Collector outputs 24 V, ≤ 150 mA
switch point [°C]/ reset point [°C],
hysteresis ≥ 2 K, Switch-on-/Switch-off-delay,
NC/ NO
IO-Link revision
V1�1, downward compatible to V1�01
SIO mode
yes, supported
Transmission rate
COM2 (38�400 Baud)
Storage temperature
-20 - 80 °C
Permissible humidity
95 % r�H� max� (non condensing)
Power requirement
24 V DC +10 % / -20 % Ripple ≤ 200 mV
Housing material
Stainless steel
Weight
approx� 0�4 kg
Connectivity
5-pin connection M12 (A coded)
Protection
IP 65 according to DIN 40050
with screwed plug
Configuration parameters
Emissivity ratio 80 - 120 %
Emissivity ε 10 - 110 %
Smoothing function t
98
- before Max/min memory 0�1 - 10 s
- after Max/min memory 0�1 - 999�9 s
Peak hold function 0�1 - 999�9 s
DTD function