1-32
Return to
Section Topics
2400S-903-01 Rev. E / September 2011
Section 1: Introduction
Series 2400 SourceMeter® Quick Start Guide
Remote command programming
SCPI commands
SCPI commands for basic non-binning limit testing are listed in Table 17.
NOTE Table 17 does not provide a complete listing of limit commands. See
Sections 12 and 18 of the 2400 Series SourceMeter User’s Manual
for complete documentation.
Programming example
The programming example in Table 18 tests 1k
Ω
resistors. If the tested resistor is within 5% of it’s
nominal value, it will pass the test. Otherwise the test will fail.
Table 1-17
SCPI commands; basic non-binning limit testing
Command
*
Description
*
For all limit tests:
:CALCulate2:DATA?
Acquire limit test reading(s).
Limit 1 test:
:CALCulate2:LIMit:STATe <b>
Enable/disable Limit 1 test; <b> = ON or OFF.
:CALCulate2:LIMit:COMPliance:FAIL <.name>
Set Limit 1 fail condition; <name> = IN (fail if in
compliance) or OUT (fail if not in compliance).
:CALCulate2:LIMit:FAIL?
Query Limit 1 test result (0 = pass, 1 = fail).
Limit 2, 3, 5-12 tests:
:CALCulate2:LIMitX:STATe <b>
Enable/disable Limit X test; <b> = ON or OFF.
:CALCulate2:FEED <name>
Select input path; <name> = CALCulate[1],
VOLTage, CURRent or RESistance.
:CALCulate2:LIMitX:LOWer <n>
Set lower limit for Limit X; <n> = limit.
:CALCulate2:LIMitX:UPPer <n>
Set upper limit for Limit X; <n> = limit.
:CALCulate2:LIMitX:FAIL?
Query Limit X test result (0 = pass, 1 = fail).
*LIMitX = LIMit2, LIMit3, LIMit5 through LIMit12.