background image

EXAMPLE A

Rear connection directly into a chimneybreast or 
a masonry chimney, e.g. a Heda Chimney.

Mark

 

the centre for the hole in the wall for the flue. 

Check that the height agrees with the stove's connec

-

tion height. Make a hole with a diameter of approx. 

180 mm using a drill and a chisel.

Install a pre-bushing of approx. ∅160 (not included) 

using heat-resistant mortar. The connecting pipe 

(not included) is measured and cut, so the end of the 

pipe ends at the level of the chimney's flue after it is 

installed.

When the stove is installed, the pipe has to be con

-

nected to the stove's connection sleeve using a seal

-

ant and tightly caulked with oakum or mineral wool 

between the flue and the pre-bushing. 

NOTE! Brick-

ing the pipe into the chimney is not allowed.

EXAMPLE B

Rear connection through a flammable wall

The connection is made in the same way as in ex

-

ample A, with the exception that the connecting pipe 

passes through a flammable wall.

The flammable wall therefore, must be furnished with 

a shaft with fire retardant lining (Masterboard, Minerit 

or equivalent) and be insulated with at least 100-mm-

thick fireproof insulation around the connection pipe. 

Thus, there must not be any flammable material closer 

than 100 mm from the flue.

If the outer diameter of the flue is ∅128 mm, the shaft 

must be at least 328 mm x 328 mm.

3. UNPACKING 

The K700 is delivered on a pallet broken down into 

the following parts: 

Stove completely assembled              

 

1x

Hearth plates, glove etc.

 (Box in hearth)

 

 

1x

Sleeve connector  

 

 

 

1x

Cover plate  

 

 

 

 

1x

(Not used with top connection or the hotplate accessory)

 

The stove is secured on the pallet via a fixing plate in 

the base. If you want, some parts of the stove can be 

dismantled to make installation easier. The procedure 

for this is described in the following steps.

1. Remove the cast iron/soapstone top

- 6 -

Chimney

Pre-bushing

Cut 

off

Concrete Wall

Connecting pipe

Chimney

Pre-bushing

Cut 

off

Wall

Fire proof insulation 100mm

Shaft of fire retardant 

material

Insulation

Summary of Contents for K700

Page 1: ...K700 Installation Instructions Care and firing instructions...

Page 2: ...plate Outdoor air supply Flue Chimney connections PREPARATIONS 5 7 Flue connections for rear and top installation Floor plate and outdoor air connection Unpacking Dismantling INSTALLATION INSTRUCTION...

Page 3: ...sional perform the installa tion Our dealers can recommend suitable fitters You can find information about our dealers on www keddy se The Clean Air Act 1993 and Smoke Control Areas Under the Clean Ai...

Page 4: ...an use Keddy s own floor plate or floor glass These are installed after completing the installa tion of the stove OUTDOOR AIR SUPPLY For the combustion of wood air supply air is required The K700 can...

Page 5: ...stallation Alternative 2 Top installation Height from the floor to the centre of the flue at the rear 665 mm Height from the floor to the height of the connection top 820 mm Outer diam of the rear top...

Page 6: ...he connecting pipe passes through a flammable wall The flammable wall therefore must be furnished with a shaft with fire retardant lining Masterboard Minerit or equivalent and be insulated with at lea...

Page 7: ...heck horizontally and vertically with the help of a spirit level is on the hearth s sealing plate Tip The stove is vertical and horizontal when the door stays open at an opening an gle greater than 90...

Page 8: ...s leave at least 10 mm of venti lated space between the top of the stove and the chimney s insulation outer steel jacket see illustration The first section of the chimney is normally half insulated ap...

Page 9: ...harmful for both people and the environment BEFORE FIRING WHEN THE STOVE IS NEW During the first week firing can be started carefully Start with one to two fires during the first couple of days A par...

Page 10: ...t that you turn off the ventilation temporarily or open a window until the negative pressure has dissipated If there is insufficient burning material in the firebed to light a new fuel charge excessiv...

Page 11: ...NSIONS AND PERFORMANCE Height 820 mm Width 564 mm Depth 425 mm Weight 170 kg Height centre rear connection 665 mm Height top connection 820 mm Outer dimensions connection sleeve 125 mm Useful efficien...

Page 12: ...12 www keddy se Rev 1 01 05 2015...

Reviews: