Installation and connection
ServoOne User Manual SERCOS II and III
ID no.: 1108.26B.3-00 Date: 04/2020
Installation and connection
4.2.4
Meaning of the LEDs
RJ-45 socket LEDs
There are two LEDs on each RJ-45 socket. These have the following significance.
LED
Meaning
1 (green)
Link LED:
x
Off: No link
No connection to another bus user
x
On: Link active
There is a connection to another bus user
2 (orange)
Activity LED:
x
Off: No activity
No data transfer
x
Flashing: Activity
Data transfer active
Table 4.2
Significance of the LEDs on the RJ-45 socket
LED H1
Colour 1
Colour 2
State
Description
Comment
Green
Green
On
CP4 no error
Green
Off
Flashing with
4 Hz
Loopback
Change from fast forward to loopback
Red
Green
Flashing with
4 Hz
Communication error
Dependent on S-0-1003 (flashes red
to green)
Red
Red
On
S III C1D
(Class 1 diagnostic).
See “Error messages in state class 1
Orange
Orange
On
CP0 . .CP3
Orange
Off
Flashing with
4 Hz
Identification
(Bit 15 in the device controller) is used
for address assignment, configuration
errors or other identification purposes.
Off
Off
Off
No SERCOS III
communication
CPx: Communication phase
Table 4.3
Significance of LED H1
4.3 Indication of the operating states via
7-segment display
D1
D2
Meaning
Parameter
System states
8.
8.
Device in reset state
0.
Self-initialisation on device startup
(Start)
S.
*)
1.
1) Not ready to switch on (no DC link voltage)
(NotReadyToSwitchOn)
S.
*)
2.
1) Switch on disabled (DC link in order, power stage not
ready)
(SwitchOnDisabled)
3.
Ready to switch on (power stage ready)
(ReadyToSwitchOn)
4.
Switched on (device is electrically live)
2)
(SwitchedOn)
5.
Drive ready (power applied to drive and drive ready for
reference value input)
2)
(OperationEnable)
6.
Quick stop
2)
(QuickStopActive)
7.
Fault reaction active
2)
(FaultReactionActive)
E
R
Fault (see below)
(Fault)
If there is a fault, the following is displayed alternately
E
R.
Indication for fault or fault that cannot be acknowledged
X
Y
Fault number (decimal)
X
Y
Fault location (decimal)
1)
S.
flashes if the function STO (Safe Torque Off) is active, indication extinguishes if function is inactive.
*) This is not a "safe indication" in the context of EN 61800-5-2.
2) The dot flashes when the power stage is active.
Table 4.4
Operating states via 7-segment display
Summary of Contents for ServoOne junior
Page 10: ...10 ServoOne User Manual SERCOS II and III ID no 1108 26B 3 00 Date 04 2020 ...
Page 54: ...54 ServoOne User Manual SERCOS II and III ID no 1108 26B 3 00 Date 04 2020 ...
Page 78: ...78 ServoOne User Manual SERCOS II and III ID no 1108 26B 3 00 Date 04 2020 ...
Page 84: ...84 ServoOne User Manual SERCOS II and III ID no 1108 26B 3 00 Date 04 2020 ...
Page 85: ...85 ServoOne User Manual SERCOS II and III ID no 1108 26B 3 00 Date 04 2020 ...