9
Technical data
9.1
In general
Power supply voltage:
24 V DC from the front connection (19.2 V to 30
V, acc. to EN 61131-2:2007),
24 V DC vom K-Bus,
5 V DC vom K-Bus.
Overvoltage category:
II
Equipment class:
III according to EN 61131-2:2007
Power supply of the digital IOs:
Via front connection
Addressing at K-Bus:
Via 16-digit address switch, on the side
Displays on the front panel:
8 signal status-LEDs for digital IOs
Connection terminals:
Open terminals, grid dimensions 5.08 mm
Max number of add-on modules:
to CP modules: 8,
to a BL 210/A: 2,
to a BL 250/A: 5.
Max. power consumption K Bus 24 V:
0 W
Max. power consumption K Bus 5 V:
0,7 W
9.2
Environmental conditions
Operating temperature:
+5 °C to +55 °C
Storage temperature:
-40 °C to 70 °C
Relative humidity of air:
10 % to 95 % (non condensing)
Vibration resistance:
according to EN 61131-2:2007
Shock resistance:
according to EN 61131-2:2007
9.3
Position counter
Counter depth:
32 Bit.
9.4
Motor bridges (PWM outputs)
Number of motor bridges:
2
Resolution:
8-bit
Output type:
Digital outputs
Nominal voltage:
24 V DC
Processing time:
1 ms
Nominal current:
1 A
MM 280/A
Technical data
© KEBA 2011
Project engineering manual 1.04
25
Summary of Contents for Kemro MM 280/A