40
Control circuit
Info
Connection to programming system !
A correct adjustment is important for the programming system connection. The IP address
can be set by parameter Et01. The subnet mask is set by parameter Et11.
Default:
IP-Address 192.168.0.100
Subnet mask 255.255.255.0
A power-on reset is required after changing!
The interface supports automatic polarity detection, AutoCrossover and automatic speed de-
tection, adjustable by parameter Et15.
Attention
Protect P6 against unauthorized access !
Each user within a network can take access to the control with knowledge of the IP address.
The write access via port 8001 can be restricted by parameter et09.
4.3.10 Fieldbus interface X6C
The unit indentification (chapter 1.8) shows the fieldbus interface that is installed in
COMBIVERT P6.
4.3.10.1
Profibus DP
Sub-D-9
Socket
5
4
3
2
1
9
8
7
6
LD5 LD6
Pin
Signal
Description
1
–
reserved
2
–
reserved
3
RxD/TxD-P transmit/receive signal P
4
–
reserved
5
DGND
Data reference potential
6
VP
supply voltage for terminating resistor
7
–
reserved
8
RxD/TxD-N transmit/receive signal N
9
–
reserved
Housing
–
capacitively earthed
LED
Signal
Light pattern Meaning
LD5
Ready
on
ready for operation
off
not ready for operation
LD6
Data
on
data are transmitted by the PROFI-
BUS
off
no data transmission
Figure 33: PROFIBUS DP interface
The connection is described in the installation instruction (8.021). These can be downloaded
from www.profibus.com.
Summary of Contents for COMBIVERT P6
Page 2: ......
Page 47: ...47 Notes...