4.1.1 Terminals
All SubD connectors have screw sockets with UNC 4-40 thread (tightening torque 0.4 Nm).
Shield connection rails 3 x 10 mm are available for strain relief / shield connection of the
control cables. Commercially available shield connection clamps (screw- or spring type) of
suitable size or cable ties can be used on them.
4.1.1.1 Connecting wires to X1A and X1B
1. Strip cable suitably
(see chapter 4.2.1)
Use ferrules if re-
quired.
x
2. Push cable into the round slot,
that no wires can be seen from
the outside.Cable is automati-
cally locked.
Figure 7:
Connecting wires to X1A and X1B
4.1.1.2 Connecting wires to X2A and X2B
Cross-section
Ferrule
Metal sleeve length Stripping length
0.50 mm
2
without plastic case
(DIN 46228/4)
10 mm
12 mm
0.75 mm
2
12 mm
14 mm
1.00 mm
2
12 mm
15 mm
1.50 mm
2
without plastic case
(DIN 46228/1)
10 mm
10 mm
0.14…1.5 mm
2
single- or fine-wire
without wire-end ferrule
–
10…15 mm
Table 2:
Wire-end ferrule and stripping length at X2A and X2B
Attention
A safe clamping can not be guaranteed when using shorter wire-end
ferrules.
Info
KEB generally recommends the use of wire-end ferrules in industrial
environments.
•
Press pusher by hand. Insert connecting wires into the respective hole, that no single
wires can be seen from the outside or bend outward.
A first resistance must be overcome when inserting. Release the pusher.
•
Check that the connecting wire is fixed and can not be pulled-out. It is important to en
-
sure that the connecting wire and not the insulation is clamped. The connecting wire can
also be inserted without pressing the pusher in case of cross-sections upto 1.00 mm².