Inverter
Copper conductors
19H6
60°C or 75°C
20H6
21H6
24H6
75°C
25H6
27H6
28H6
• These supply modules are only for use with drive modules that are part of the
COMBIVERT H6 series.
• Brake Resistors provided in the end-use shall be controlled by manufacturer and
type designation, and separately subjected to above specified tests, due to differ
-
ences in brake resistors construction, even with identical rating.
• Connection of an External Temperature Sensor was not evaluated.
• Maximum heatsink temperature for H6 models shall be maintained at the following
listed values via a liquid cooled system:
Inverter
Maximum heatsink
temperature
19H6
80°C
20H6
21H6
60°C
24H6
80°C
25H6
60°C
27H6
80°C
28H6
60°C
• Suitable for use on a Circuit Capable of delivering not more 18k rms Symmetrical
Amperes, 480 Volts maximum when protected by fuses as specified in the follow
-
ing table:
53
CERTIFICATION
All manuals and user guides at all-guides.com