16
3.5
Control Board Compact/General
3.5.1 X2A Control Terminal Strip
• Tightening torque 0,22...0,25 Nm (2 lb inches)
• Use shielded/drilled cables
• Lay shield on one side of the inverter onto earth potential
Installation and Connection
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 16 17 18 19 20 21 22 23
24 25 26 27 28 29
PIN Function
Nam e Description
1
+ Set value input
AN1+ Differential voltage inputs 0...±10 VDC; Ri = 55kOhm
2
- Set value input
AN1- AN1: Setting of the analog set value
3
+ Analog input
AN2+ AN2: no function at KEB factory settings
4
- Analog input
AN2-
Progr. analog outputs
0...±10 VDC / max. 5 mA; defined by the manufacturer
5
Analog output 1
AO1
Output of the actual output frequency 0...±100 Hz
6
Analog output 2
AO2
Output of the apparent current 0...2 x I
N
7
+ 10 V Output
CRF
Reference voltage for set value poti (max. 4 mA)
8
Analog Mass
COM
Mass for analog in- and outputs
9
Analog Mass
COM
Mass for analog in- and outputs
Prog. Digital inputs
Function of the inputs is defined by the manuf acturer
10
Fixed frequency 1 (CP.19) I1
13...30 VDC ±0% smoothed; Ri: 2,1 kOhm; scan time 1 ms
11
Fixed frequency 2 (CP.20) I2
I1 + I2 = Fixed frequency 3 (CP.21)
12
External fault
I3
Input for external fault setting (E.EF)
13
DC-braking
I4
Activates the DC-braking (CP.22/23)
14
Forw ard
F
Preset rotation;
15
Reverse
R
Forw ard has priority
16
Control release/ Reset
ST
Pow er modules are enabled; reset at opening
17
Reset
RST
Reset; only w hen an error occurs
Digital outputs
max. 50 mA; function is defined by the manufacturer
18
Transistor output 1
O1
sw itched at factual = fset
19
Transistor output 2
O2
Ready signal (sw itched as long as no error occurs)
20
24 V-Output
U
out
Supply of the programmable inputs
21
20...30 V-Input
U
in
Voltage input for external supply
22
Digital Mass
0V
Potential for digital in- /outputs
23
Digital Mass
0V
Potential for digital in- /outputs
24
Relay 1 / NO contact
RLA
Programmable relay output (CP.31)
25
Relay 1 / NC contact
RLB
Load ability max. 30 VDC / 0.01...1A
26
Relay 1 / sw itching contact RLC
Factory setting: Fault relay
27
Relay 2 / NO contact
FLA
Programmable relay output (CP.32)
28
Relay 2 / NC contact
FLB
Load ability max. 30 VDC / 0.01...1A
29
Relay 2 / sw itching contact FLC
Factory setting: Frequency dependent sw itch