14
1
5
7
8 10 11 14 15 16 20 22
24 25 26 27 28 29
Installation and Connection
3.4
Control Board Basic
3.4.1 X2A Control Terminal Strip
• Tightening torque 0,22...0,25 Nm (2 lb inches)
• Use shielded/drilled cables
• Lay shield only on the inverter side onto
earth potential
X2A
PIN Function
Nam e Description
1
+ Set value input
AN1+ Differential voltage inputs 0...±10 VDC; Ri = 55kOhm
2
- Set value input
AN1-
AN1: Setting of the analog set value
Progr. analog outputs
0...±10 VDC / max. 5 mA; defined by the manufacturer
5
Analog output 1
AO1
Output of the actual output frequency 0...±100 Hz
7
+ 10 V Output
CRF
Reference voltage for set value poti (max. 4 mA)
8
Analog Mass
COM
Mass for analog in- and outputs
Prog. Digital inputs
Function of the inputs is defined by the manufacturer
10
Fixed frequency 1 (CP.19) I1
13...30 VDC ±0% smoothed; Ri: 2,1 kOhm; scan time 2 ms
11
Fixed frequency 2 (CP.20) I2
I1 + I2 = Fixed frequency 3 (CP.21)
14
Forw ard
F
Preset rotation;
15
Reverse
R
Forw ard has priority
16
Control release/ Reset
ST
Pow er modules are enabled; reset at opening
20
24 V-Output
U
out
Supply of the programmable inputs
22
Digital Mass
0V
Potential for digital in- /outputs
24
Relay 1 / NO contact
RLA
Programmable relay output (CP.31)
25
Relay 1 / NC contact
RLB
Load ability max. 30 VDC / 0.01...1A
26
Relay 1 / sw itching contact RLC
Factory setting: Fault relay
27
Relay 2 / NO contact
FLA
Programmable relay output (CP.32)
28
Relay 2 / NC contact
FLB
Load ability max. 30 VDC / 0.01...1A
29
Relay 2 / sw itching contact FLC
Factory setting: Frequency dependent sw itch
Summary of Contents for COMBIVERT F5
Page 1: ...C O M B I V E R T 11 2004 00 F5 0EM KB02 C D E F GB I Installation Guideline Housing B...
Page 29: ...29...
Page 30: ...30...
Page 31: ......