GB - 30
CP-Parameter
5.2
Parameter description for Multi and Application with encoder interface
Display Parameter
Setting range
Resolution Default Unit ENTER Based on
CP.00 Password Input
0...9999
1
–
–
–
ud.01
CP.01 Encoder 1 speed
±4000
0.125
0
rpm
–
ru.09
CP.02 Setpoint display
±4000
0.125
0
rpm
–
ru.01
CP.03 Inverter state
0...255
1
0
–
–
ru.00
CP.04 Apparent current
0...6553.5
0.1
0
A
–
ru.15
CP.05 Apparent current / peak value
0...6553.5
0.1
0
A
–
ru.16
CP.06 Actual torque
±10000.00
0.01
0
Nm
–
ru.12
CP.07 Actual DC voltage
0...1000
1
0
V
–
ru.18
CP.08 DC-link voltage / peak value
0...1000
1
0
V
–
ru.19
CP.09 Output voltage
0...778
1
0
V
–
ru.20
CP.10 Speed control configuration
0(off)...5
1
0 (off)
–
–
cs.00
CP.11 DASM Rated speed
0...32000
1
LTK
rpm
–
dr.24
CP.12 DASM rated frequency
0.0...1600.0
0.1
LTK
Hz
–
dr.25
CP.13 DASM rated current
0.0...1100.0
0.1
LTK
A
–
dr.23
CP.14 DASM Rated voltage
120...830
1
LTK
V
–
dr.02
CP.15 DASM Rated cos (phi)
0.50...1.00
0.01
LTK
–
–
dr.04
CP.16 DASM Rated power
0.10...1000.00
0.01
LTK
kW
–
dr.03
CP.17 Load motor dependent parameter
0...3
1
1
–
E
fr.10
CP.18 Boost
0.0...25.5
0.1
LTK
%
–
uf.01
CP.19 rated frequency
0...400
0.0125
50
Hz
–
uf.00
CP.20 Encoder 1 (inc/r)
1…65535
1
2500
Inc
E
ec.01
CP.21 Encoder 1 rotation
0...19
1
0
–
E
ec.06
CP.22 Maximum speed
0...4000
0.125
2100
rpm
–
op.10
CP.23 Step value 1
±4000
0.125
100
rpm
–
op.21
CP.24 Step value 2
±4000
0.125
-100
rpm
–
op.22
CP.25 Acceleration time
0.00...300.00
0.01
5,00
s
–
op.28
CP.26 Deceleration time
-0.01...300.00
0.01
5,00
s
–
op.30
CP.27 S-curve time
0.00(off)...5.00
0.01
0.00(off)
s
–
op.32
CP.28 Torque reference source
0...6
1
2
–
E
cs.15
CP.29 Absolute torque reference
±32000,00
0.01
LTK
Nm
–
cs.19
CP.30 KP speed
0...32767
1
300
–
–
cs.06
CP.31 KI speed
0...32767
1
100
–
–
cs.09
CP.32 Switching frequency
1...LTK
1
LTK
–
E
uf.11
CP.33 Relay output 1 / Function
0...92
1
4
–
E
do.02
CP.34 Relay output 2 / Function
0...92
1
2
–
E
do.03
CP.35 Limit switch / stopping mode
0...6
1
6
–
–
pn.07
CP.36 External Fault / stopping mode
0...6
1
0
–
–
pn.03
CP.3 Inverter status
In parameter „inverter status“ the actual operating condition of the frequency inverter is
displayed (e.g. constant running forward, standstill). In the case of an error the current error
message is displayed, even if the display has already been reset with ENTER (error-LED
on the operator is still blinking). Status messages and information about the cause and
removal are to be found in "www.keb.de".