GB - 37
CP-Parameter
Value Function
63 Absolut value ANOUT1 > switching level
1)
64 Absolut value ANOUT2 > switching level
1)
65 ANOUT1 > switching level
1)
66 ANOUT2 > switching level
1)
70 Driver voltage activ (safety relay)
73 Absolut active power > switching level
1)
74 Active power > switching level
1)
Unlisted values are only for application mode
1)
Switching level of CP.33 = 100; switching level of CP.34 = 4
CP.35 Limit switch / stopping mode
This parameter determines the reaction of the drive to terminal X2A.14 (F) and/or X2A.15
(R), which are programmed as limit switches. The reaction of the drive is shown in the
table below.
CP.35 Display Response
Restart
0
E.PRx Immediate disabling of modulation
Remove fault,
reset
1
A.PRx Quick stopping / disabling of modulation after
reaching speed 0
2
A.PRx Quick stop / holding torque at speed 0
3
A.PRx Immediate disabling of modulation
Autoreset, if no fault
is present
4
A.PRx Quick stopping / disabling of modulation after
reaching speed 0
5
A.PRx Quick stop / holding torque at speed 0
6
None No effect to the drive,
fault is ignored !
Inapplicable
CP.36 External Fault / stopping mode
With the external error monitoring external units can take direct influence on the drive.
This parameter determines the response of the drive to a signal at terminal X2A.12 (I3)
according to following table.
CP.36 Display Response
Restart
0
E.PRx Immediate disabling of modulation
Remove fault,
reset
1
A.PRx Quick stopping / disabling of modulation after
reaching speed 0
2
A.PRx Quick stop / holding torque at speed 0
3
A.PRx Immediate disabling of modulation
Autoreset, if no fault
is present
4
A.PRx Quick stopping / disabling of modulation after
reaching speed 0
5
A.PRx Quick stop / holding torque at speed 0
6
None No effect to the drive, fault is ignored
!
Inapplicable