32
GB
When switching on KEB COMBIVERT the value of parameter CP.1
appears. (See Drive mode to switch the keyboard function)
The
function key
(FUNC)
changes between the
parameter value and
parameter number.
With
UP
( ) and
DOWN
(
) the value of the
parameter number is
increased / decreased with
changeable
parameters.
Principally during a change, parameter values are immediately accepted
and stored non-volatile. With some parameters it is not useful, that the
adjusted value immediately be accepted. When this type of parameter is
changed, then a point appears behind the last digit.
By pressing
ENTER
the
adjusted value is
accepted and non-volatile
stored.
If a malfunction occurs during operation, then the actual display is
overwritten by the alarm message. The alarm message in the display is
reset by ENTER.
With ENTER the error message is only reset in the display. In
order to reset an error oneself, the cause must be removed
and a reset on terminal X1.14 or a power-on reset must occur.
In the Inverter status display (CP. 2) the error is still displayed.
Operation of the Unit
4.1.2 Keyboard
error
ENTER
F/R
START
STOP
START
STOP
FUNC.
SPEED
ENTER
F/R