Id-Text
Name
Parameter index
os13
operator state
0x208D
Meaning
Displays the status of the power unit, as well as the image of the
power unit parameter of the control board.
Type
Variable
Data length
8 bit
Access
read
Coding
Bit 0
reserved
Bit 1...2
PU-conf.-ID status 0: Power unit-ID unknown
2: Power unit-ID OK
4: Power unit-ID incorrect
Bit 3...5
PU-image status
0: PU image not initialised
1: write PU image
3: PU image changed
4: PU image initialised
5: PU image check
6: PU image not available
Bit 6...15 reserved
Standard value: 0
Note
-
Id-Text
Name
Parameter index
os14
store state
0x208E
Meaning
By writing of value "0" non-volatile parameters are saved imme-
diately. After completion of the storage the value jumps to status
"1". If at the end of the download lists in COMBIVIS the value "0"
comes before value "1", COMBIVIS will send the value as long
as the inverter finishes storing.
Type
Variable
Data length
8 bit
Access
read / write
Coding
0: busy
1: ready
2: off
Standard value: 1
Note
-