GB - 9
2.3.2 400 V class
Inverter size
10
12
Housing size
B
Phases
3
Output rated power
[kVA]
4
6.6
Max. rated motor power
[kW]
2.2
4
Output rated current
[A]
5.8
9.5
Max. short time current
[A]
10.4
17
OC-tripping current
[A]
12.5
21
Input rated current
[A]
8
13
Max. permissible mains fuse (inert)
[A]
16
20
Rated switching frequency
[kHz]
4
4
Max. switching frequency
[kHz]
8
8
Power loss at nominal operating
[W]
64
95
Input rated voltage
1)
[V]
400 (UL:400…480)
Input voltage range U
mains
[V]
305…528 ±0
Mains forms
TN, TT, IT
2)
, Delta
3)
Mains frequency
[Hz]
50…60 ±2
Output voltage
[V]
3 x 0…U
mains
Output frequency
[Hz]
0…400
Min. motor line cross section
[mm
2
]
1.5
2.5
Max. motor line length (shielded)
[m] 30 at limit value class C2
With intergrated braking transistor
Typically braking resistor
[Ω]
270
150
Maximal braking current
[A]
10
10
Leakage current with internal filter (at nOP)
[mA]
6
1) at mains voltage ≥460 V multiply the nominal current with factor 0.86.
2) insulating resistance at mains form IT = 2 MΩ
3) on inquiry