3.4.7
EMC filter
EMC filter
U
in_max_ac
= 3 x 480 V;
f
N
= 50 Hz;
T
_max
=
45°C
Filter
Fig-
ure
I
N
Ilk
50
Ilk
max
P
d
Radio interference level up to switch-
ing frequency and motor line length
Weight
in A
in mA in mA in W
in kg
20E6T60-3000
1
100
<3
30
50
C1 8 kHz
50 m
C1 16 kHz
30 m
C2 16 kHz
100 m
–
22E6T60-3000
2
150
<3
45
80
C1 4 kHz
50 m
C1 16 kHz
30 m
C2 16 kHz
50 m
–
24E6T60-3000
2
200
<3
30
100
C1 4 kHz
50 m
C1 8 kHz
30 m
C2 8 kHz
30 m
–
28E4T60-1001
3
410
60
220
50
C2 2 kHz
30m
C2 8 kHz
30m
C2 16kHz
30m
18.5
I
N
= rated current;
I
lk_50
= leakage current at 50 Hz;
I
lk_max
= max. leakage current (phase - PE);
P
d
= power dissipation
Figure 1
Figure 2
Figure 3
240
8
220
9
130
160
175,5
121,5
200
190
74,3
321 280
11
10
260
15
150
Table 10: EMC filter
3.4.7.1 Connection cross sections and tightening torques
Filter
Mains connection 3-phase
Tightening torque
PE
Tightening torque
20E6T60-3000
16…50 mm² (AWG 6-0)
6...8 Nm
(60 lb inch)
M8
12 Nm (105 lb inch)
22/24E6T60-3000
35…95 mm² (AWG 4-0)
15 Nm
(130 lb inch)
M10
25 Nm (220 lb inch)
28E4T60-1001
M10
25 Nm (220 lb inch)
[recommended]
M12
40 Nm (354 lb inch)
[recommended]
Table 11:
Connection cross sections and tightening torques
37
MECHANICAL INSTALLATION
Summary of Contents for COMBIVERT 19H6 Series