View rear side of the device
Size C / S
X1A
X1B
X1A
PE
PE
X1b
Terminal connection
Function
Conductor
cross-section
Tightening torque
X1A
U
Connection to the filter.
Connect inphase.
0.2...6 mm²
AWG 24-10
0.7 Nm
6.2 lb inch
V
W
X1b
BR+
Connection for
24 V DC brake
0.25...1.5 mm²
AWG 28-16
0.25 Nm
2.2 lb inch
BR-
T1
Connection for PTC / KTY
filter temperature monitoring
T2
PE
Connection for
shielding / earthing
M6 stud
for ring crimp
connector
1.3 Nm
11.5 lb inch
Figure 12: View of the bottom of the device size C / S
The terminal blocks meet the requirements of