2.1
Technical Data of the 400V Class
2.2
Ambient Conditions
2.3
Input Rated Current
*
=
Rated operation
**
=
At rated voltage > = 460V multiply the rated current with factor 0,86
***
=
Upto connection power >= 30kW motor rating power power at frequency inverter
Voltage class
400V
Rated voltage
400V
Permissible range
360V to 440V
Mains frequency
50Hz/ 60Hz **
Overload capacity
150% for 60 sec.
All 10 min.
EN 60146-1-1/
Rating class III
Efficiency @ *
> 99%***
THDI @ *
<= 8%
cos phi *
aprox. 0,99
Storage temperature
-25...70 °C (-13...158 °F)
Operating temperature
-10...45 °C (14...113 °F)
Model / protective system (EN 605
IP20
Environment (IEC 664-1)
Pollution degree 2
Climatic categorie (EN 60721-3-3)
3K3
Part No.
Irating [A]
Prating [kW]
Weight [kg]
Terminal [mm
2
]
PE-connection
12.Z1.C04-1000
10
4
12,3
4
M6
13.Z1.C04-1000
12,6
5,5
13,3
4
M6
14.Z1.C04-1000
17,3
7,5
17,6
4
M6
15.Z1.C04-1000
25,2
11
25,3
16
M6
16.Z1.C04-1000
34,7
15
36,3
16
M8
17.Z1.C04-1000
44,1
18,5
46,3
16
M8
18.Z1.C04-1000
52,5
22
55,5
35
M8
19.Z1.C04-1000
63
30
63,2
35
M8
20.Z1.C04-1000
79
37
73,6
35
M8
21.Z1.C04-1000
95
45
92,4
50
M10
22.Z1.C04-1000
121
55
107,7
50
M10
23.Z1.C04-1000
158
75
159,7
95
M10
24.Z1.C04-1000
189
90
171,5
95
M10
25.Z1.C04-1000
221
110
214,5
95
M10
26.Z1.C04-1000
263
132
237,1
150
M10
27.Z1.C04-1000
315
160
272,1
150
M10
28.Z1.C04-1000
390
200
340
2*150
M12
29.Z1.C04-1000
460
250
471,9
2*240
M12
Summary of Contents for COMBILINE