Instruction Sheet

Variable Speed - Setpoint (00-VS)

“00” and Load Match

®

 Cartridge Circulators

102-143

SUPERSEDES: May 1, 2010 

EFFECTIVE: October 1, 2010

Plant ID# 001-3811 
The Variable Speed - Setpoint “00” Cartridge Circulator (00-VS) is a microprocessor-based pump designed to regulate the tempera-
ture to a system through variable speed injection mixing. The 00-VS regulates the temperature to provide a fixed setpoint or a fixed 
temperature difference (

T) for heating or cooling applications. For fixed setpoint operation, a boiler return sensor can be connected 

to protect the boiler against flue gas condensation.
In order to properly accomplish this mixing method, the following piping details should be considered.

Applications

The following are typical applications the 00-VS supports. The 00-VS includes a five DIP package with DIP siwtches 1, 3 and 5 used 
to configure the control for a given application. These DIP switch configurations are indicated to the right of the application drawing.
DIP switch 2 is used to select the appropriate temperature range for the desired setpoint target. DIP switch 4 is used to select the 
controls variable speed output response. It is recommended that a normal response (DIP 4 = Off) is used. This will aid in reducing 
potential thermal expansion issues in a system. If it is desired for the control to achieve the setpoint or 

T target quicker, a more 

aggressive variable speed output response can be selected by setting DIP switch 4 to On.

The 00-VS adjusts the variable speed output to the fancoil pump P1 to maintain a setpoint discharge air temperature at the duct 
sensor whenever a heat demand is present. While the control is operating to maintain the setpoint temperature, the variable speed 
output is adjusted to ensure the boiler inlet temperature is above the boiler inlet minimum setpoint.

The 00-VS adjusts the variable speed output to the P1 pump to maintain a setpoint temperature at the supply sensor whenever 
a heat demand is present. While the control is operating to maintain the setpoint temperature, the variable speed output is also 
adjusted to ensure the boiler inlet temperature is above the boiler inlet minimum setpoint.

The 00-VS adjusts the variable speed output to the P1 pump to maintain at least a setpoint temperature at the boiler sensor (S3) 
whenever a heat demand is present. The control adjusts the variable speed output towards zero speed as long as the temperature 
is above the setpoint. 

The 00-VS adjusts the variable speed output to the P1 pump to maintain at least a setpoint temperature at the boiler sensor 
(S3) whenever a heat demand is present. The control adjusts the variable speed output towards full speed as long as the 
temperature is above the setpoint. Note: This application illustrates variable flow conditions through the boiler. This con-
trol  configuration  should  only  be  used  with  a  heat  source  which  is  not  flow  sensitive,  such  as  a  high  mass  cast  iron  boiler.

Supply
Sensor 
(S1 or S2)

Boiler
Sensor (S3)

P1

“00-VS”

DIP 5 = Off (Linear Output Characteristic)
DIP 3 = Off (Direct Acting)
DIP 1 = Off (Setpoint Target)

Off

On

1

2

3

4

5

Boiler
Sensor (S3)

Duct
Sensor
(S1 or S2)

P1

“00-VS”

DIP 5 = On (Equal Percentage Output Characteristic)
DIP 3 = Off (Direct Acting)
DIP 1 = Off (Setpoint Target)

Off

On

1

2

3

4

5

Boiler

Sensor (S3)

High Mass
Boiler

P1

“00-VS”

DIP 5 = Off (Linear Output Characteristic)
DIP 3 = Off (Direct Acting)
DIP 1 = Off (Setpoint Target)

Off

On

1

2

3

4

5

Boiler
Sensor (S3)

P1

“00-VS”

DIP 5 = Off (Linear Output Characteristic)
DIP 3 = On (Reverse Acting)
DIP 1 = Off (Setpoint Target)

Off

On

1

2

3

4

5

00-VS-1

00-VS-3

00-VS-2

00-VS-4

A Taco resource – saving product

Summary of Contents for 00-VS

Page 1: ...ture the variable speed output is adjusted to ensure the boiler inlet temperature is above the boiler inlet minimum setpoint The 00 VS adjusts the variable speed output to the P1 pump to maintain a setpoint temperature at the supply sensor whenever a heat demand is present While the control is operating to maintain the setpoint temperature the variable speed output is also adjusted to ensure the b...

Page 2: ...unwanted heat transfer primary secondary piping tech niques are used as shown in figure 1 This piping arrangement requires that the injection piping be at least one pipe diameter smaller than the piping of the boiler and system loops There must be no more than 4 pipe diameters between the tees in the boiler and system loops Note 1 in order to prevent ghost flow when the injection pump is off and t...

Page 3: ...est signal is present at the Heat Request Ht Req terminals A heat request signal may be provided by external end switches from zone valves or ZVC SR series zone controls applying a dry contact closure or a powered 24 V ac signal across the Ht Req terminals If end switches or switching relays are not available a jumper must be installed to provide a heat request Once a heat request signal is presen...

Page 4: ...al where the first and last temperatures from the selected temperature range corresponds to 1 and 10 respectively on the RANGE dial with the temperature increasing in 5ºF increments Note Only one of the sensors S1 or S2 can be connected in this mode of operation Boiler Protection When either system sensor S1 or system sensor S2 is installed for setpoint operation and the boiler return sensor S3 is...

Page 5: ...his signal may come from zone valve end switches Taco ZVC SR series zone controls or thermostats When a thermostat is connected directly to the heat request terminals use dry contact style i e mechanical digital hard wired or digital battery operated Sensors Do not apply power to these terminals as this will damage the PC Board The wiring terminals for the sensors may be removed for ease of instal...

Page 6: ...ce In addi tion to this the actual temperature must be measured with a good quality digital thermometer First measure the temperature using the thermometer and then measure the resistance of the sensor at the 00 VS The wires from the sensor must not be connected to the PC Board while this test is performed The wiring terminals are easily removed by pulling them from the PC Board Using the chart be...

Page 7: ...s between the cartridge flange and motor 6 Make sure the replacement cartridge corresponds to the full circulator product number A complete parts list is available from your local plumbing supply wholesaler 7 Reassemble the circulator using the new gasket and bolts supplied 8 Follow the Installation procedure to start up the circulator Replacing Integral Flow Check IFC Assembly if applicable 1 Dis...

Page 8: ...replacement products and parts which are substantially similar in design and functionally equivalent to the defective product or part Taco reserves the right to make changes in details of design construc tion or arrangement of materials of its products without notification TACO OFFERS THIS WARRANTY IN LIEU OF ALL OTHER EXPRESS WARRANTIES ANY WARRANTY IMPLIED BY LAW INCLUDING WARRANTIES OF MERCHANT...

Reviews: