Service Manual for Medium Frequency Sine-wave Filters
GB-6
2.5
Exchange of the capacitors
2.5.1
Spare parts list
If the result of the test requires an exchange of the capacitors, they can be ordered from
KEB by the following material number:
Table 2.5.1
Capacitor
Rated capacitance
Tightening torque
0090339-1061
3 x 10,0 µF
3 x screw terminal
M10 => 10 Nm
M12 => 15 Nm
Connection
M12 => 7 Nm
0090339-1260
3 x 12,0 µF
0090339-1561
3 x 15,0 µF
0090339-3651
3 x 3,6 µF
0090339-3361
3 x 33,0 µF
0090339-4751
3 x 4,7 µF
0090339-0860
3 x 8,0 µF
2.5.2
Preparations
If not be done before measurement the following steps are necessary:
•
switch system de-energized
•
secure against restart
•
await one minute for discharge of the capacitors
• clean sine-wave filter from dust and other contaminations
2.5.3
Disassembly of the old capacitors
•
remove heat-shrinkable tube with knife
•
unscrew connection cable
• remove fixing bolts
•
remove capacitor
•
execute insulation test in accordance with 2.4.3 (if required)
2.5.4
Installation of new capacitors
•
insert capacitor
• tighten fixing bolt in accordance with table 2.5.1
•
pull heat-shrinkable tube over the connection cables
•
tighten connection cable in accordance with table 2.5.1
•
lock heat-shrinkable tube with hot-air fan
2.6
Disposal
The capacitors are lead-free and use M-DBT as dielectric. Disposal of old capacitors must
be done in accordance with the local regulations.