KE2 Temp + Defrost Installation Manual Download Page 6

Q.1.20 February 2016

Page 6

KE2 Temp 

+ Defrost 

(pn 20611)

For 

Medium Temperature

 Applications with 

Air Defrost

Installation Manual

© Copyright 2016 KE2 Therm Solutions, Inc., Washington, Missouri 63090

Basic Setpoints

Setpoint 

Description

Minimum

Default 

Maximum

tS

Temperature Setpoint

-50

°

F (-45

°

C)

 

35

°

F

100

°

F (38

°

C)

diF 

Differential

1

°

F (1K)

2

°

F

30

°

F

 

(17K)

CSH 

Maximum Compressor Starts/Hour

5 (Off)*

6

10

dPd 

Defrost Per Day

0

6

12, CUS**

dFt

Defrost Time

0 min

15 min

720 min

HAO 

High Alarm Offset

1

°

F

 

(1K)

5

°

F

10

°

F

 

(6K)

LAO 

Low Alarm Offset

1

°

F

 

(1K)

3

°

F

10

°

F

 

(6K)

tAd 

Temp Alarm Delay

1 min

90 min

180 min

Adr 

Mod Bus Address

1

1

247

Unt 

Units for temp display 

FAH

FAH

CEL

*Selecting fewer than 5 compressor starts per hour results in the starts per hour feature being turned off. The compressor will then function on 

temperature only.

** Selecting CUS (custom) unlocks additional Setpoints. See Advanced Setpoints table.

Advanced Setpoints 

- includes setpoints only visible when CUS (custom) is selected under dPd (defrosts per day)

Setpoint 

Description

Minimum

Default 

Maximum

tS

Temperature Setpoint

-50

°

F (-45

°

C)

35

°

F

100

°

F (38

°

C)

diF 

Differential

1

°

F

 

(1K)

2

°

F

30

°

F

 

(17K)

CSH 

Maximum Compressor Starts/Hour

5 (Off)*

6

10

dPd 

Defrost Per Day

 0

6

12, CUS

d12

Start time of Defrost #12

00

dis (disabled)

23,dis (disabled)

d11

Start time of Defrost #11

00

dis

23,dis

d10

Start time of Defrost #10

00

dis

23,dis

d9

Start time of Defrost #9

00

dis

23,dis

d8

Start time of Defrost #8

00

dis

23,dis

d7

Start time of Defrost #7

00

dis

23,dis

d6

Start time of Defrost #6

00

dis

23,dis

d5

Start time of Defrost #5

00

dis

23,dis

d4

Start time of Defrost #4

00

dis

23,dis

d3

Start time of Defrost #3

00

dis

23,dis

d2

Start time of Defrost #2

00

dis

23,dis

d1

Start time of Defrost #1

00

dis

23,dis

tod

Time of Day

0.0

12.0

23.5

dFt

Defrost Time

0 min

15 min

720 min

HAO 

High Alarm Offset

1

°

F

 

(1K)

5

°

F

10

°

F

 

(6K)

LAO 

Low Alarm Offset

1

°

F

 

(1K)

3

°

F

10

°

F

 

(6K)

tAd 

Temp Alarm Delay

1 min

90 min

180 min

Adr 

Mod Bus Address

1

1

247

Unt 

Units for temp display 

FAH

FAH

CEL

*Selecting fewer than 5 compressor starts per hour results in the starts per hour feature being turned off. The compressor will then function on 

temperature only.

See pa

ge 7 f

or det

ailed C

ust

om Defr

ost s

etup instruc

tions 

**CUS -  S

etpoin

ts displa

y when CUS selec

ted

Summary of Contents for Temp + Defrost

Page 1: ...ltage wires matched to the load of the liquid line solenoid compressor and the controller wire labeling numbers colors etc additional wire ties 18 gauge twisted shielded pair if extending sensor wires...

Page 2: ...plicity in mind The controller accepts 120V 208 240V to power the controller and 12V 240V solenoid voltage via the liquid line solenoid relay through the lower conduit connection The temperature senso...

Page 3: ...the controller will be breaking one leg of the power One leg of incoming power L1 supply for the liquid line solenoid should be connected to the common terminal of the liquid line solenoid relay the...

Page 4: ...e temperature sensor terminal is located on the cover s circuit board and is permanently attached The temperature sensor input consists of the right two terminals Although the terminals are labeled an...

Page 5: ...tions KE2 Temp Use the up and to change the setpoint ENTER Press to move between the digits to accelerate the changes ENTER Press and hold to confirm each setpoint change BACK Press to escape Only vis...

Page 6: ...mum Default Maximum tS Temperature Setpoint 50 F 45 C 35 F 100 F 38 C diF Differential 1 F 1K 2 F 30 F 17K CSH Maximum Compressor Starts Hour 5 Off 6 10 dPd Defrost Per Day 0 6 12 CUS d12 Start time o...

Page 7: ...the nearest 10 minutes See exam ples below Examples then press Use the up arrow and down arrow to set the time STEP 7 Press the button to save set tings and return to the main screen room temp will b...

Page 8: ...rm Solutions 12 Chamber Drive Washington MO 63090 1 888 337 3358 www ke2therm com Q 1 20 February 2016 Page 8 KE2 Temp Defrost pn 20611 For Medium Temperature Applications with Air Defrost Installatio...

Reviews: