Q.1.20 February 2016
Page 6
KE2 Temp
+ Defrost
(pn 20611)
For
Medium Temperature
Applications with
Air Defrost
Installation Manual
© Copyright 2016 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Basic Setpoints
Setpoint
Description
Minimum
Default
Maximum
tS
Temperature Setpoint
-50
°
F (-45
°
C)
35
°
F
100
°
F (38
°
C)
diF
Differential
1
°
F (1K)
2
°
F
30
°
F
(17K)
CSH
Maximum Compressor Starts/Hour
5 (Off)*
6
10
dPd
Defrost Per Day
0
6
12, CUS**
dFt
Defrost Time
0 min
15 min
720 min
HAO
High Alarm Offset
1
°
F
(1K)
5
°
F
10
°
F
(6K)
LAO
Low Alarm Offset
1
°
F
(1K)
3
°
F
10
°
F
(6K)
tAd
Temp Alarm Delay
1 min
90 min
180 min
Adr
Mod Bus Address
1
1
247
Unt
Units for temp display
FAH
FAH
CEL
*Selecting fewer than 5 compressor starts per hour results in the starts per hour feature being turned off. The compressor will then function on
temperature only.
** Selecting CUS (custom) unlocks additional Setpoints. See Advanced Setpoints table.
Advanced Setpoints
- includes setpoints only visible when CUS (custom) is selected under dPd (defrosts per day)
Setpoint
Description
Minimum
Default
Maximum
tS
Temperature Setpoint
-50
°
F (-45
°
C)
35
°
F
100
°
F (38
°
C)
diF
Differential
1
°
F
(1K)
2
°
F
30
°
F
(17K)
CSH
Maximum Compressor Starts/Hour
5 (Off)*
6
10
dPd
Defrost Per Day
0
6
12, CUS
d12
Start time of Defrost #12
00
dis (disabled)
23,dis (disabled)
d11
Start time of Defrost #11
00
dis
23,dis
d10
Start time of Defrost #10
00
dis
23,dis
d9
Start time of Defrost #9
00
dis
23,dis
d8
Start time of Defrost #8
00
dis
23,dis
d7
Start time of Defrost #7
00
dis
23,dis
d6
Start time of Defrost #6
00
dis
23,dis
d5
Start time of Defrost #5
00
dis
23,dis
d4
Start time of Defrost #4
00
dis
23,dis
d3
Start time of Defrost #3
00
dis
23,dis
d2
Start time of Defrost #2
00
dis
23,dis
d1
Start time of Defrost #1
00
dis
23,dis
tod
Time of Day
0.0
12.0
23.5
dFt
Defrost Time
0 min
15 min
720 min
HAO
High Alarm Offset
1
°
F
(1K)
5
°
F
10
°
F
(6K)
LAO
Low Alarm Offset
1
°
F
(1K)
3
°
F
10
°
F
(6K)
tAd
Temp Alarm Delay
1 min
90 min
180 min
Adr
Mod Bus Address
1
1
247
Unt
Units for temp display
FAH
FAH
CEL
*Selecting fewer than 5 compressor starts per hour results in the starts per hour feature being turned off. The compressor will then function on
temperature only.
See pa
ge 7 f
or det
ailed C
ust
om Defr
ost s
etup instruc
tions
**CUS - S
etpoin
ts displa
y when CUS selec
ted