KE2 Temp + Defrost Installation Manual Download Page 2

© Copyright 2016 KE2 Therm Solutions, Inc., Washington, Missouri 63090

Q.1.20 February 2016

Page 2

KE2 Temp 

+ Defrost 

(pn 20611)

For 

Medium Temperature

 Applications with 

Air Defrost

Installation Manual

When wiring the controller first remove the dis-

play by loosening the four corner screws. The 

display is connected to the lower board by a 

short ribbon cable.

Caution: The board may be damaged if exces-

sive force is used when removing the cover.

1

1

Wiring the Controller

The KE2 Temp was designed with simplicity in 

mind. The controller accepts 120V / 208-240V 

to power the controller and 12V - 240V solenoid 

voltage via the liquid line solenoid relay through 

the lower conduit connection. The temperature 

sensor and communication wires are attached 

via the upper conduit connector. 

After the four screws have been detached from 

the lower section, the cover may be gently 

moved to the side. 

2

2

Next remove the high voltage protective cover. 

There are two screws holding it in place. 

3

3

With the high voltage cover removed, the two 

screw terminal connectors can be seen. The 

2-position connector is the controller’s power 

supply. The voltage selector switch should be 

positioned to match the voltage supplied.

4

4

Summary of Contents for Temp + Defrost

Page 1: ...ltage wires matched to the load of the liquid line solenoid compressor and the controller wire labeling numbers colors etc additional wire ties 18 gauge twisted shielded pair if extending sensor wires...

Page 2: ...plicity in mind The controller accepts 120V 208 240V to power the controller and 12V 240V solenoid voltage via the liquid line solenoid relay through the lower conduit connection The temperature senso...

Page 3: ...the controller will be breaking one leg of the power One leg of incoming power L1 supply for the liquid line solenoid should be connected to the common terminal of the liquid line solenoid relay the...

Page 4: ...e temperature sensor terminal is located on the cover s circuit board and is permanently attached The temperature sensor input consists of the right two terminals Although the terminals are labeled an...

Page 5: ...tions KE2 Temp Use the up and to change the setpoint ENTER Press to move between the digits to accelerate the changes ENTER Press and hold to confirm each setpoint change BACK Press to escape Only vis...

Page 6: ...mum Default Maximum tS Temperature Setpoint 50 F 45 C 35 F 100 F 38 C diF Differential 1 F 1K 2 F 30 F 17K CSH Maximum Compressor Starts Hour 5 Off 6 10 dPd Defrost Per Day 0 6 12 CUS d12 Start time o...

Page 7: ...the nearest 10 minutes See exam ples below Examples then press Use the up arrow and down arrow to set the time STEP 7 Press the button to save set tings and return to the main screen room temp will b...

Page 8: ...rm Solutions 12 Chamber Drive Washington MO 63090 1 888 337 3358 www ke2therm com Q 1 20 February 2016 Page 8 KE2 Temp Defrost pn 20611 For Medium Temperature Applications with Air Defrost Installatio...

Reviews: