KE2 Temp + Defrost Installation Manual Download Page 3

Q.1.20 February 2016

Page 3

© Copyright 2016 KE2 Therm Solutions, Inc., Washington, Missouri 63090

KE2 Temp 

+ Defrost 

(pn 20611)

For 

Medium Temperature

 Applications with 

Air Defrost

Installation Manual

5

5

6

7

Replace high voltage shield after wiring is 

completed.

The liquid line solenoid/compressor relay ac-

cepts a variety of input voltages and is not re-

quired to match the controller’s input. See table 

for relay ratings. The relay uses the 3-position 

screw terminal to make the connection on the 

board. This relay is designed to control smaller 

compressors directly. It may also control either 

the liquid line solenoid or as a pilot to the com-

pressor contactor.When connecting the wires to 

the relay, the controller will be breaking one leg 

of the power.

One leg of incoming power (L1) supply for the 

liquid line solenoid should be connected to the 

common terminal of the liquid line solenoid 

relay, the right most terminal connection. The 

other leg of the incoming power (L2) should be 

connected directly to the solenoid lead. The re-

maining lead from the solenoid should be con-

nected to the NO (normally open) terminal, the 

leftmost terminal location.

Proper wiring practices must be followed. Local 

wiring codes take precedence over any informa-

tion in this bulletin. 

6

Connect line (L1) to the right terminal position 

and neutral (L2) to the left terminal position.

Voltage Table

Outputs:

(1) Relay

Single Pole Double 

Throw

Normally Open

Normally Closed

120V

240V

120V

240V

FLA

30A

30A

N/A

10A

LRA

98A

80A

N/A

20A

Resistive

N/A

30A

N/A

30A

Horsepower

1 hp

2 hp

1/4 hp

1/2 hp

Pilot Duty

800VA

720VA

290VA

360VA

Summary of Contents for Temp + Defrost

Page 1: ...ltage wires matched to the load of the liquid line solenoid compressor and the controller wire labeling numbers colors etc additional wire ties 18 gauge twisted shielded pair if extending sensor wires...

Page 2: ...plicity in mind The controller accepts 120V 208 240V to power the controller and 12V 240V solenoid voltage via the liquid line solenoid relay through the lower conduit connection The temperature senso...

Page 3: ...the controller will be breaking one leg of the power One leg of incoming power L1 supply for the liquid line solenoid should be connected to the common terminal of the liquid line solenoid relay the...

Page 4: ...e temperature sensor terminal is located on the cover s circuit board and is permanently attached The temperature sensor input consists of the right two terminals Although the terminals are labeled an...

Page 5: ...tions KE2 Temp Use the up and to change the setpoint ENTER Press to move between the digits to accelerate the changes ENTER Press and hold to confirm each setpoint change BACK Press to escape Only vis...

Page 6: ...mum Default Maximum tS Temperature Setpoint 50 F 45 C 35 F 100 F 38 C diF Differential 1 F 1K 2 F 30 F 17K CSH Maximum Compressor Starts Hour 5 Off 6 10 dPd Defrost Per Day 0 6 12 CUS d12 Start time o...

Page 7: ...the nearest 10 minutes See exam ples below Examples then press Use the up arrow and down arrow to set the time STEP 7 Press the button to save set tings and return to the main screen room temp will b...

Page 8: ...rm Solutions 12 Chamber Drive Washington MO 63090 1 888 337 3358 www ke2therm com Q 1 20 February 2016 Page 8 KE2 Temp Defrost pn 20611 For Medium Temperature Applications with Air Defrost Installatio...